Gliffy | ||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
|
GIC E-Stop
This indicates the status of the Emergency Stop from the GIC. Axis motion is inhibited if this is active. The indicator also functions as a GOTO button that will open the GIC E-Stop Display to enable further investigation of the cause.
Seismic Alarm
This indicates the status of the Seismic Alarm signal from the GIC.
Info |
---|
This signal is not currently used. |
Fire Alarm
This indicates the status of the Building Fire Alarm. Axis motion is inhibited if this is active.
GIC Permissive
This indicates the status of various GIC interlocks. Axis motion is inhibited if this is active.
Info |
---|
This signal is not currently used. |
If this signal is active then communications between the GIC and Enclosure LIC are not working properly.
E-Stop
This indicates the status of the Local Emergency Stop Devices. Axis motion is inhibited if this is active. The indicator also functions as a GOTO button that will open the Enclosure E-Stop Display to enable further investigation of the cause.
Final Limits
The Enclosure Altitude final limits monitor the position of the Enclosure Azimuth Axis to ensure it does not exceed mechanical limits.
If the Enclosure Altitude Axis has exceeded the allowable final limits the Enclosure Azimuth Axis must be manually moved out of the final limit.
Switch control to ‘Local’.
The Enclosure Altitude Axis Final Limit must be bypassed entering a passcode in the EMCS PLC. Set tag
Alt_Limit_Final_Reached_PassWord
to 7654321.Manually drive the Enclosure Altitude Axis out of the limit while visually monitoring the motion.
Note |
---|
Failure to ensure proper motion out of the limit may result is damage to the Enclosure Altitude Axis. |
Speed Limit
The maximum speed of the Enclosure Altitude Axis is monitored. If the speed limit is exceed the axis will be inhibited.
Shutter Seals
This indicator shows the status of the Shutter Seals. If the seals are not fully deflated the axis will be inhibited.
Trapped Keys
This indicator shows whether the proper trapped key is in place. Either of these conditions must be true:
Trapped Key 'A' is in Cabinet 001
Trapped Key 'B' is in Cabinet 503
TEOA Platform
This indicator shows the status of the TEOA platform drawbridge and guard rail.
Info |
---|
This signal is not currently used. |
Transfer Bridge
This indicator shows the status of the Transfer Bridge Gate. The gate must be properly closed or the axis will be inhibited.
Rear Door
This indicator shows the status of the rear door on the telescope level. The door must be properly closed or if it is open then the light curtain safety sensors must not be interrupted or the axis will be inhibited.
Overtension
This indicator shows the status of the Enclosure Altitude Cable Wrap overtension sensor.
Info |
---|
This signal is not currently used. |
Output Faulted
This indicator shows the status of the Drive Enable and Drive Power output safety functions. If either is faulted it must be cleared before enabling the axis.