Versions Compared

Key

  • This line was added.
  • This line was removed.
  • Formatting was changed.

The concentrated focused beam of sunlight produced by a 4.0m mirror is around 16.9 kW. Enough energy to boil a liter of water in about 3 seconds. The concentrated focused beam can and has cause caused damage to telescope components at or near the prime focus and at other points along the optical path.

There are to is a similar functions function that can be confused for this Light Path Safety Function. The Top End Optical Assembly Safety Function serves to protect the components of the Heat Stop Assembly quickly by deploying the Heat Stop Safety Shutter then activating the this Light Path safety functionSafety Function.

To achieve the required SIL rating, two redundant methods of blocking the light path are employed. The employed—the M1 Cover and the Aperture Cover. Each system is independent and have unrelated back-up power sources to minimize common cause failures.

Light Path Safety Function

Safety Function

Light Path

Hazard

Focused sunlight along optical path

Triggering Event

Any of the following:

safety function
  • Safety Function activated

  • Safety shutter not fully stowed

  • Telescope Altitude permissive removed

  • Telescope Azimuth permissive removed

  • M1 Cover UPS failure

  • Aperture cover drive ‘not ready’

  • Separation angle between Sun and optical path > 1.5R

  • Heat Stop fuse wire not OK

  • Instrument Field-of-view misconfigured

Priority

The Light Path shall take priority over all other control functions.

Modes

When light path is not blocked

  • Sun above horizon and

  • Enclosure Aperture pointing within 25° of the Sun

Reaction

Block light path using sequence:

Close M1 Cover then

Close Aperture Cover

Safe State

Aperture Cover closed

M1 Mirror Cover closed

Required Integrity

SIL2

Gliffy
imageAttachmentIdatt2274525195
macroId4722ac50-088a-4e44-b62f-2d68d58ef504
baseUrlhttps://nso.atlassian.net/wiki
nameLight Path (Safe State)
diagramAttachmentIdatt2274852873
containerId2158821409
timestamp1692205134558

...

The operation of the Light Path Safety Function is defined in the GIC_GLX code in the Light_Path routine, in the SafetyProgram, in the SafetyTask of the GIC_GLX controller.

Time

Reaction

Comment

0:00

15s

M1 Cover starts closing

0:15

135s

Aperture Cover starts closing

M1 Cover must be closed.

2:30

Aperture Cover must be closed.

The M1 is commanded to close when the trigger conditions are met.

After the M1 Cover is fully closed or 15 seconds later, which ever whichever comes first, the Aperture cover is commanded to close. If the M1 cover fails to fully close within 15 seconds an M1 Cover Timeout Fault is generated and latched.

...