Top End Optical Assembly Safety Function

Safety Function

Top End Optical Assembly

Hazard

Focused sunlight on components of the TEOA

Triggering Event

Any of the following:

  • Heat Stop over temperature

  • Heat Absorber over temperature

  • Heat Stop low coolant flow

  • Safety shutter not fully stowed

Priority

The Light Path shall take priority over all other control functions.

Modes

When light path is not blocked

  • Sun above horizon and

  • Enclosure Aperture pointing within 25° of the Sun

Reaction

Block light path using sequence:

Heat Stop Assembly Safety Shutter

Close M1 Cover then

Close Aperture Cover

Safe State

Heat Stop Assembly Safety Shutter closed

Aperture Cover closed

M1 Mirror Cover closed

Required Integrity

SIL2

The operation of the TEOA Safety Function has been integrated into the GIC_GLX code in the Light_Path routine, in the SafetyProgram, in the SafetyTask of the GIC_GLX controller.

If the event of a heat absorber overtemp, heat stop overtemp, or heat stop low coolant flow. The safety shutter will be triggered first which will then trigger the remaining Light Path reactions.

Time

Reaction

Comment

0:00

2.5s

Safety Shutter starts closing

0:02.5

15s

M1 Cover starts closing

Safety Shutter must be closed.

0:17.5

135s

Aperture Cover starts closing

M1 Cover must be closed.

2:32.5

Aperture Cover must be closed.

The reaction begins by closing the Safety Shutter. When the safety shutter moves from the fully open position the M1 Cover closing is triggered. If the safety shutter fails to move after being commanded, 2.5 seconds later the M1 Cover is commanded to close anyway. If the safety shutter fails to close within 2.5 seconds a Safety Shutter Timeout Fault is generated and latched.

...