Skip to end of banner
Go to start of banner

Differences in GuardLogix Controllers

Skip to end of metadata
Go to start of metadata

You are viewing an old version of this page. View the current version.

Compare with Current View Page History

Version 1 Next »

1756-L6xS

  • firmware version v. 17 - 20

  • battery back-up of user application

1756-L7xS vs. 1756-L6xS

  • firmware version v. 20+

  • non-volatile memory is SD card instead of CompactFlash

  • Replaceable Energy Storage module for battery back-up of user application

1756-L8xES vs. 1756-L7xS

  • firmware version v. 31+

  • Non-replaceable Energy Storage module for battery back-up of user application

  • Safety Signature has changed instead of 32-bit hexadecimal value it is a 32 character hexadecimal value stored as a SINT(33).

  • Built-in Ethernet port

  • Task Monitor Tool do longer works. To get similar data there is a web page on the controller itself.

See also:

http://literature.rockwellautomation.com/idc/groups/literature/documents/rm/1756-rm100_-en-p.pdf

http://literature.rockwellautomation.com/idc/groups/literature/documents/um/1756-um001_-en-p.pdf

  • No labels