Electrical Panel Schedules
Electrical Panel Schedules Revision-controlled Vault Location
Copy of current master - Electrical Panel Schedules Update_M3_Site_APR-2021_m3resp
https://docs.google.com/spreadsheets/d/1GkHyiFRGbLoqfKdhqKLtkFy7hq9V9R0yl19XrHABr10/edit?usp=sharing Simplified panel schedules, updated as of 2024-03-20. The circuit identifications are more up-to-date than the above, but missing its detail.
For redlines:
Please download a copy of the current master.
Mark up electronically or by hand.
Add a new line to the table with details and a copy of the redlined pages.
Date of Redline Creation | Affected Sheet # | Initials of Author | Description of Update | Redline Update File |
---|---|---|---|---|
2022-02-24 | SB-UPSL4B | EGS | M3/M4/M6 feed optics thermal rack circuit changed from 1P-120V to 2P-208V due to overcurrent condition with original circuit and ePDU. Branch circuit moved from SB-UPSL4B-25 to new 30A breaker on 22,24. Details in TOE-145. |
|
|
|
|
|
|