General FMS Trouble Shooting
General FMS Trouble Shooting
BACnet
The Ignition BACnet driver will occasionally fail to communicate with some devices after a power outage. The quick fix is to log into the Ignition server browser interface. Go to the Config section, the BACNET where you’ll find local devices. Select edit next to the local device called FMSHMI. Without changing any settings, select save. Typically this is enough to trigger it to reestablish communications. Otherwise, restart the server.