Communications between the Optical Support Subsystem (OSS) LIC and the GIC consists of one tag, an array of 128 BOOL values for various logic values (see below).

OSS to GIC bit assignments

OSS_to_GIC is a user-defined type SAFETY_ARRAY which consists of the the safety connection status and an array of 128 BOOL. Assignments are listed below:

Tag Name

Data Type

Description

OSS_to_GIC

UDT_SafetyArray

 

OSS_to_GIC.Connection_Status

CONNECTION_STATUS

 

OSS_to_GIC.Data[0]

BOOL

Telescope Mount Emergency Stop OK

OSS_to_GIC.Data[1]

BOOL

Telescope Mount PLC I/O OK (LEDstatus=3)

OSS_to_GIC.Data[2]

BOOL

reserved

OSS_to_GIC.Data[3]

BOOL

reserved

OSS_to_GIC.Data[4]

BOOL

reserved

OSS_to_GIC.Data[5]

BOOL

reserved

OSS_to_GIC.Data[6]

BOOL

reserved

OSS_to_GIC.Data[7]

BOOL

reserved

OSS_to_GIC.Data[8]

BOOL

OSS on sun

OSS_to_GIC.Data[9]

BOOL

reserved

OSS_to_GIC.Data[10]

BOOL

reserved

OSS_to_GIC.Data[11]

BOOL

reserved

OSS_to_GIC.Data[12]

BOOL

reserved

OSS_to_GIC.Data[13]

BOOL

reserved

OSS_to_GIC.Data[14]

BOOL

reserved

OSS_to_GIC.Data[15]

BOOL

reserved

OSS_to_GIC.Data[16]

BOOL

Heat Stop Safety Shutter Open

OSS_to_GIC.Data[17]

BOOL

Heat Stop Safety Shutter Closed

OSS_to_GIC.Data[18]

BOOL

Heat Stop Safety Shutter Permissive

OSS_to_GIC.Data[19]

BOOL

Heat Stop Safety Temperature OK

OSS_to_GIC.Data[20]

BOOL

Heat Stop Safety Pressure OK

OSS_to_GIC.Data[21]

BOOL

reserved

OSS_to_GIC.Data[22]

BOOL

reserved

OSS_to_GIC.Data[23]

BOOL

reserved

OSS_to_GIC.Data[24]

BOOL

Heat Stop Installed

OSS_to_GIC.Data[25]

BOOL

M2 Installed

OSS_to_GIC.Data[26]

BOOL

reserved

OSS_to_GIC.Data[27]

BOOL

reserved

OSS_to_GIC.Data[28]

BOOL

reserved

OSS_to_GIC.Data[29]

BOOL

reserved

OSS_to_GIC.Data[30]

BOOL

reserved

OSS_to_GIC.Data[31]

BOOL

reserved

OSS_to_GIC.Data[32]

BOOL

M5 Temperature OK

OSS_to_GIC.Data[33]

BOOL

Heat Stop Fuse Wire OK

OSS_to_GIC.Data[34]

BOOL

GOS small FOV selected

OSS_to_GIC.Data[35]

BOOL

reserved

OSS_to_GIC.Data[36]

BOOL

reserved

OSS_to_GIC.Data[37]

BOOL

reserved

OSS_to_GIC.Data[38]

BOOL

reserved

OSS_to_GIC.Data[39]

BOOL

reserved

OSS_to_GIC.Data[40]

BOOL

reserved

OSS_to_GIC.Data[41]

BOOL

reserved

OSS_to_GIC.Data[42]

BOOL

reserved

OSS_to_GIC.Data[43]

BOOL

reserved

OSS_to_GIC.Data[44]

BOOL

reserved

OSS_to_GIC.Data[41]-->[127]

BOOL

not used

  • No labels