This section is based on TN-0157 GIS Programming. This Tech Note contain configuration details and programming styles that were not an absolute requirement or specification. It was to layout guidelines for GIS programming to promote consistency.

The reason this is a Tech Note rather than a Spec was that specifications were also contract requirements. Changing contractual requirements after the contract was signed was an onerous process so using a technical note to detail configuration information was the route chosen.

Network Configuration

Stratix 8300 switch address are configured as follows:

System

Address

Hostname

Global Interlock Controller

10.4.0.1

GIS_Switch

Telescope Mount Drive Assembly

10.4.0.201

Tel_Switch

Coudé Rotator System

10.4.0.202

Rot_Switch

Optical Support System

10.4.0.203

OSS_Switch

Instruments System

10.4.0.204

Inst_Switch

Enclosure (lower)

10.4.0.205

Enc_Switch

Facility

10.4.0.206

Fac_Switch

Facility Thermal System

10.4.0.207

FTS_Switch

Enclosure (upper)

10.4.0.209

Enc_Switch2

Virtual LANs (VLANs) are configured as follows:

System

VLAN Name

VLAN ID

Address Space

Global Interlock Controller

VLAN0100

100

10.4.0.0/24

Telescope Mount Drive Assembly

VLAN0101

101

10.4.1.0/24

Coudé Rotator System

VLAN0102

102

10.4.2.0/24

Optical Support System

VLAN0103

103

10.4.3.0/24

Instruments System

VLAN0104

104

10.4.4.0/24

Enclosure

VLAN0105

105

10.4.5.0/24

Facility Equipment

VLAN0106

106

10.4.6.0/24

Facility Thermal System

VLAN0107

107

10.4.7.0/24

Development LIC1

VLAN0108

108

10.4.8.0/24

Development LIC2

VLAN0109

109

10.4.9.0/24

Setup

VLAN0192

192

192.168.0.0/16

IP Addressing

GIC to LIC communications

Communications between the GIC and the LIC consist of tag of the user-defined type UDT_SafetyArray. This is essentially an array of 128 bits plus CONNECTION_STATUS.

User Defined Type UDT_SafetyArray

GIC to Enclosure bit assignments

Tag Name

Description

GIC_to_ENC

GIC_to_ENC.Connection_Status

GIC_to_ENC.Data[0]

Global Emergency Stop OK

GIC_to_ENC.Data[1]

Fire Alarm OK

GIC_to_ENC.Data[2]

Seismic Alarm OK

GIC_to_ENC.Data[3]

reserved

GIC_to_ENC.Data[4]

Reset Command from GIC

GIC_to_ENC.Data[5]

reserved

GIC_to_ENC.Data[6]

reserved

GIC_to_ENC.Data[7]

reserved

GIC_to_ENC.Data[8]

Inner Pier Hazardous Zone Locked

GIC_to_ENC.Data[9]

Mezzanine Level  Hazardous Zone Locked

GIC_to_ENC.Data[10]

Coudé Lab Hazardous Zone Locked

GIC_to_ENC.Data[11]

Utility Level Hazardous Zone Locked

GIC_to_ENC.Data[12]

Catwalk Hazardous Zone Locked

GIC_to_ENC.Data[13]

Service Ring Hazardous Zone Locked

GIC_to_ENC.Data[14]

Enclosure Floor Hazardous Zone Locked

GIC_to_ENC.Data[15]

Telescope Hazardous Zone Locked

GIC_to_ENC.Data[16]

Upper Enclosure Hazardous Zone Locked

GIC_to_ENC.Data[17]

reserved

GIC_to_ENC.Data[18]

reserved

GIC_to_ENC.Data[19]

reserved

GIC_to_ENC.Data[20]

Enclosure Azimuth OK to move

GIC_to_ENC.Data[21]

Enclosure Azimuth Full Speed OK

GIC_to_ENC.Data[22]

reserved

GIC_to_ENC.Data[23]

reserved

GIC_to_ENC.Data[24]

Enclosure Altitude OK to move

GIC_to_ENC.Data[25]

reserved

GIC_to_ENC.Data[26]

reserved

GIC_to_ENC.Data[27]

reserved

GIC_to_ENC.Data[28]

Aperture Cover OK to move

GIC_to_ENC.Data[29]

Aperture Cover OK to open

GIC_to_ENC.Data[30]

reserved

GIC_to_ENC.Data[31]

reserved

GIC_to_ENC.Data[32]

Bridge Crane OK to move

GIC_to_ENC.Data[33]

reserved

GIC_to_ENC.Data[34]

reserved

GIC_to_ENC.Data[35]

reserved

GIC_to_ENC.Data[36]

Jib Crane OK to move

GIC_to_ENC.Data[37]

reserved

GIC_to_ENC.Data[38]

reserved

GIC_to_ENC.Data[39]

reserved

GIC_to_ENC.Data[40]

Rear Door OK to move

GIC_to_ENC.Data[41]

Rear Door OK to open

GIC_to_ENC.Data[42]

reserved

GIC_to_ENC.Data[43]

reserved

GIC_to_ENC.Data[44]-->[127]

not used

Enclosure to GIC bit assignments

Tag Name

Description

ENC_to_ENC

ENC_to_GIC.Connection_Status

ENC_to_GIC.Data[0]

Enclosure Emergency Stop OK

ENC_to_GIC.Data[1]

Enclosure PLC I/O OK (LEDStatus=3)

ENC_to_GIC.Data[2]

reserved

ENC_to_GIC.Data[3]

reserved

ENC_to_GIC.Data[4]

Enclosure Azimuth Ready

ENC_to_GIC.Data[5]

Enclosure Altitude Ready

ENC_to_GIC.Data[6]

Enclosure Lower Maintenance trapped key in place

ENC_to_GIC.Data[7]

Enclosure Upper Maintenance trapped key in place

ENC_to_GIC.Data[8]

Enclosure Azimuth Motion Stopped

ENC_to_GIC.Data[9]

Enclosure Azimuth Safely Limited Speed

ENC_to_GIC.Data[10]

Enclosure Azimuth CW Limit

ENC_to_GIC.Data[11]

ReservedEnclosure Azimuth CCW Limit

ENC_to_GIC.Data[12]

Enclosure Altitude Motion Stopped

ENC_to_GIC.Data[13]

Enclosure Altitude local trapped key in place

ENC_to_GIC.Data[14]

Enclosure Altitude Upper Limit

ENC_to_GIC.Data[15]

Enclosure Altitude Lower Limit

ENC_to_GIC.Data[16]

Aperture Cover Closed

ENC_to_GIC.Data[17]

Aperture Cover local trapped key in place

ENC_to_GIC.Data[18]

Aperture Cover Closed Limit

ENC_to_GIC.Data[19]

Aperture Cover Open Limit

ENC_to_GIC.Data[20]

Bridge Crane Stowed

ENC_to_GIC.Data[21]

Bridge Crane local trapped key in place

ENC_to_GIC.Data[22]

reserved

ENC_to_GIC.Data[23]

reserved

ENC_to_GIC.Data[24]

Jib Crane Stowed

ENC_to_GIC.Data[25]

Jib Crane local trapped key in place

ENC_to_GIC.Data[26]

reserved

ENC_to_GIC.Data[27]

reserved

ENC_to_GIC.Data[28]

TEOA Platform Stowed

ENC_to_GIC.Data[29]

TEOA Platform local trapped key in place

ENC_to_GIC.Data[30]

reserved

ENC_to_GIC.Data[31]

reserved

ENC_to_GIC.Data[32]

Enclosure Azimuth aligned with maintenance position

ENC_to_GIC.Data[33]

Transfer Bridge Stowed

ENC_to_GIC.Data[34]

Transfer Bridge Rails Stowed

ENC_to_GIC.Data[35]

reserved

ENC_to_GIC.Data[36]

Rear Door local trapped key in place

ENC_to_GIC.Data[37]

reserved

ENC_to_GIC.Data[38]

reserved

ENC_to_GIC.Data[39]

reserved

ENC_to_GIC.Data[40]

Altitude Cable Wrap Overtension OK

ENC_to_GIC.Data[41]

Azimuth Cable Wrap Overtension OK

ENC_to_GIC.Data[42]

reserved

ENC_to_GIC.Data[43]

reserved

ENC_to_GIC.Data[44]

reserved

ENC_to_GIC.Data[41]-->[127]

not used

GIC to Telescope LIC bit assignments

The table below is the proposed structure for GIC to Enclosure communications.

Tag Name

Description

GIC_to_TEL

GIC_to_TEL.Connection_Status

GIC_to_TEL.Data[0]

Global Emergency Stop OK

GIC_to_TEL.Data[1]

Fire Alarm OK

GIC_to_TEL.Data[2]

Seismic Alarm OK

GIC_to_TEL.Data[3]

reserved

GIC_to_TEL.Data[4]

Reset Command from GIC

GIC_to_TEL.Data[5]

reserved

GIC_to_TEL.Data[6]

reserved

GIC_to_TEL.Data[7]

reserved

GIC_to_TEL.Data[8]

Inner Pier Hazardous Zone Locked

GIC_to_TEL.Data[9]

Mezzanine Level  Hazardous Zone Locked

GIC_to_TEL.Data[10]

Coudé Lab Hazardous Zone Locked

GIC_to_TEL.Data[11]

Utility Level Hazardous Zone Locked

GIC_to_TEL.Data[12]

Catwalk Hazardous Zone Locked

GIC_to_TEL.Data[13]

Service Ring Hazardous Zone Locked

GIC_to_TEL.Data[14]

Enclosure Floor Hazardous Zone Locked

GIC_to_TEL.Data[15]

Telescope Hazardous Zone Locked

GIC_to_TEL.Data[16]

Upper Enclosure Hazardous Zone Locked

GIC_to_TEL.Data[17]

reserved

GIC_to_TEL.Data[18]

reserved

GIC_to_TEL.Data[19]

reserved

GIC_to_TEL.Data[20]

Telescope Azimuth OK to move

GIC_to_TEL.Data[21]

Telescope Azimuth Full Speed OK

GIC_to_TEL.Data[22]

reserved

GIC_to_TEL.Data[23]

reserved

GIC_to_TEL.Data[24]

Telescope Altitude OK to move

GIC_to_TEL.Data[25]

Telescope Altitude Full Speed OK

GIC_to_TEL.Data[26]

reserved

GIC_to_TEL.Data[27]

reserved

GIC_to_TEL.Data[28]

M1 Cover OK to move

GIC_to_TEL.Data[29]

M1 Cover OK to open

GIC_to_TEL.Data[30]

reserved

GIC_to_TEL.Data[31]

reserved

GIC_to_TEL.Data[32]-->[127]

not used

Telescope to GIC bit assignments

Tag Name

Description

TEL_to_GIC

TEL_to_GIC.Connection_Status

TEL_to_GIC.Data[0]

Telescope Mount Emergency Stop OK

TEL_to_GIC.Data[1]

Telescope Mount PLC I/O OK (LedStatus=3)

TEL_to_GIC.Data[2]

reserved

TEL_to_GIC.Data[3]

reserved

TEL_to_GIC.Data[4]

Telescope Mount Azimuth Ready

TEL_to_GIC.Data[5]

Telescope Mount Altitude Ready

TEL_to_GIC.Data[6]

Reserved

TEL_to_GIC.Data[7]

Reserved

TEL_to_GIC.Data[8]

Telescope Mount Azimuth Motion Stopped

TEL_to_GIC.Data[9]

Telescope Mount Azimuth at Safe Speed

TEL_to_GIC.Data[10]

Telescope Mount Azimuth CW Limit

TEL_to_GIC.Data[11]

Telescope Mount Azimuth CCW Limit

TEL_to_GIC.Data[12]

Telescope Mount Altitude Motion Stopped

TEL_to_GIC.Data[13]

Telescope Mount Altitude at Safe Speed

TEL_to_GIC.Data[14]

Telescope Mount Altitude Upper Limit

TEL_to_GIC.Data[15]

Telescope Mount Altitude Lower Limit

TEL_to_GIC.Data[16]

Reserved

TEL_to_GIC.Data[17]

Reserved

TEL_to_GIC.Data[18]

Reserved

TEL_to_GIC.Data[19]

Reserved

TEL_to_GIC.Data[20]

Telescope in M1 Maintenance Position Azimuth

TEL_to_GIC.Data[21]

Telescope in M1 Maintenance Position Altitude

TEL_to_GIC.Data[22]

Telescope in TEOA Maintenance Position Azimuth

TEL_to_GIC.Data[23]

Telescope in TEOA Maintenance Position Altitude

TEL_to_GIC.Data[24]

Reserved

TEL_to_GIC.Data[25]

Reserved

TEL_to_GIC.Data[26]

Reserved

TEL_to_GIC.Data[27]

Reserved

TEL_to_GIC.Data[28]

M1 Cover Closed

TEL_to_GIC.Data[29]

M1 Cart Jacks Stowed

TEL_to_GIC.Data[30]

M1 Cover permissive

TEL_to_GIC.Data[31]

Reserved

TEL_to_GIC.Data[32]

Telescope Altitude Hazardous Zones Locked

TEL_to_GIC.Data[33]

Telescope Azimuth Hazardous Zones Locked

TEL_to_GIC.Data[34]

Telescope Azimuth Cable Wrap Alignment OK

TEL_to_GIC.Data[35]

Reserved

TEL_to_GIC.Data[36]

OSS Bridge stowed

TEL_to_GIC.Data[37]

OSS Bridge permissive

TEL_to_GIC.Data[38]

M5 Bridge stowed

TEL_to_GIC.Data[39]

M5 Bridge permissive

TEL_to_GIC.Data[40]

Nasmyth Stairs Gates Closed

TEL_to_GIC.Data[41]

Telescope Floor Y+/- Gates Closed

TEL_to_GIC.Data[42]

Telescope Tower Doors Closed

TEL_to_GIC.Data[43]

Telescope Floor Hatch Closed

TEL_to_GIC.Data[44]

Reserved

TEL_to_GIC.Data[45]-->[127]

not used

GIC to Coudé Rotator LIC bit assignments

The table below is the proposed structure for GIC to Enclosure communications.

Tag Name

Description

GIC_to_ROT

GIC_to_ROT.Connection_Status

GIC_to_ROT.Data[0]

Global Emergency Stop OK

GIC_to_ROT.Data[1]

Fire Alarm OK

GIC_to_ROT.Data[2]

Seismic Alarm OK

GIC_to_ROT.Data[3]

Heartbeat

GIC_to_ROT.Data[4]

Reset Command from GIC

GIC_to_ROT.Data[5]

Reserved

GIC_to_ROT.Data[6]

reserved

GIC_to_ROT.Data[7]

reserved

GIC_to_ROT.Data[8]

Inner Pier Hazardous Zone Locked

GIC_to_ROT.Data[9]

Mezzanine Level  Hazardous Zone Locked

GIC_to_ROT.Data[10]

Coudé Lab Hazardous Zone Locked

GIC_to_ROT.Data[11]

Utility Level Hazardous Zone Locked

GIC_to_ROT.Data[12]

Catwalk Hazardous Zone Locked

GIC_to_ROT.Data[13]

Service Ring Hazardous Zone Locked

GIC_to_ROT.Data[14]

Enclosure Floor Hazardous Zone Locked

GIC_to_ROT.Data[15]

Telescope Hazardous Zone Locked

GIC_to_ROT.Data[16]

Upper Enclosure Hazardous Zone Locked

GIC_to_ROT.Data[17]

reserved

GIC_to_ROT.Data[18]

reserved

GIC_to_ROT.Data[19]

reserved

GIC_to_ROT.Data[20]

Coudé Azimuth OK to move

GIC_to_ROT.Data[21]

Coudé Azimuth Full Speed OK

GIC_to_ROT.Data[22]

reserved

GIC_to_ROT.Data[23]

reserved

GIC_to_ROT.Data[24]-->[127]

not used

Coudé Rotator to GIC bit assignments

Tag Name

Description

ROT_to_GIC

ROT_to_GIC.Connection_Status

ROT_to_GIC.Data[0]

Rotator Emergency Stop OK

ROT_to_GIC.Data[1]

Rotator PLC I/O OK (LedStatus=3)

ROT_to_GIC.Data[2]

reserved

ROT_to_GIC.Data[3]

reserved

ROT_to_GIC.Data[4]

Rotator Azimuth Ready

ROT_to_GIC.Data[5]

reserved

ROT_to_GIC.Data[6]

reserved

ROT_to_GIC.Data[7]

reserved

ROT_to_GIC.Data[8]

Rotator Motion Stopped

ROT_to_GIC.Data[9]

Rotator at Safe Limited Speed

ROT_to_GIC.Data[10]

Rotator CW Final Limit OK (0=in limit)

ROT_to_GIC.Data[11]

Rotator CCW Limit OK  (0=in limit)

ROT_to_GIC.Data[12]

reserved

ROT_to_GIC.Data[13]

reserved

ROT_to_GIC.Data[14]

reserved

ROT_to_GIC.Data[15]

reserved

ROT_to_GIC.Data[16]

reserved

ROT_to_GIC.Data[17]

reserved

ROT_to_GIC.Data[18]

reserved

ROT_to_GIC.Data[19]

reserved

ROT_to_GIC.Data[20]

Rotator Cable Wrap Alignment OK

ROT_to_GIC.Data[21]

reserved

ROT_to_GIC.Data[22]

reserved

ROT_to_GIC.Data[23]

reserved

ROT_to_GIC.Data[24]

reserved

ROT_to_GIC.Data[25]

reserved

ROT_to_GIC.Data[26]

reserved

ROT_to_GIC.Data[27]

reserved

ROT_to_GIC.Data[28]

reserved

ROT_to_GIC.Data[29]

reserved

ROT_to_GIC.Data[30]

reserved

ROT_to_GIC.Data[31]

reserved

ROT_to_GIC.Data[32]

reserved

ROT_to_GIC.Data[33]

reserved

ROT_to_GIC.Data[34]

reserved

ROT_to_GIC.Data[35]

reserved

ROT_to_GIC.Data[36]

reserved

ROT_to_GIC.Data[37]

reserved

ROT_to_GIC.Data[38]

reserved

ROT_to_GIC.Data[39]

reserved

ROT_to_GIC.Data[40]

reserved

ROT_to_GIC.Data[41]-->[127]

not used

 

Optical Subsystem (OSS) to GIC bit assignments

Tag Name

Description

OSS_to_GIC

OSS_to_GIC.Connection_Status

OSS_to_GIC.Data[0]

OSS Emergency Stop OK

OSS_to_GIC.Data[1]

OSS PLC I/O OK (LedStatus=3)

OSS_to_GIC.Data[2]

reserved

OSS_to_GIC.Data[3]

reserved

OSS_to_GIC.Data[4]

reserved

OSS_to_GIC.Data[5]

reserved

OSS_to_GIC.Data[6]

reserved

OSS_to_GIC.Data[7]

reserved

OSS_to_GIC.Data[8]

On Sun

OSS_to_GIC.Data[9]

reserved

OSS_to_GIC.Data[10]

reserved

OSS_to_GIC.Data[11]

reserved

OSS_to_GIC.Data[12]

reserved

OSS_to_GIC.Data[13]

reserved

OSS_to_GIC.Data[14]

reserved

OSS_to_GIC.Data[15]

Reserved

OSS_to_GIC.Data[16]

Heat Stop Shutter is fully open

OSS_to_GIC.Data[17]

Heat Stop Shutter is fully closed

OSS_to_GIC.Data[18]

Heat Stop Safety Shutter permissive

OSS_to_GIC.Data[19]

Heat Stop Temperature is OK

OSS_to_GIC.Data[20]

Heat Stop Coolant Pressure is OK

OSS_to_GIC.Data[21]

Reserved

OSS_to_GIC.Data[22]

Reserved

OSS_to_GIC.Data[23]

Reserved

OSS_to_GIC.Data[24]

Heat Stop is installed

OSS_to_GIC.Data[25]

M2 is installed

OSS_to_GIC.Data[26]

Reserved

OSS_to_GIC.Data[27]

reserved

OSS_to_GIC.Data[28]

reserved

OSS_to_GIC.Data[29]

reserved

OSS_to_GIC.Data[30]

reserved

OSS_to_GIC.Data[31]

reserved

OSS_to_GIC.Data[32]

M5 Temperature is OK.

OSS_to_GIC.Data[33]

reserved

OSS_to_GIC.Data[34]

reserved

OSS_to_GIC.Data[35]

reserved

OSS_to_GIC.Data[36]

reserved

OSS_to_GIC.Data[37]

reserved

OSS_to_GIC.Data[38]

reserved

OSS_to_GIC.Data[39]

reserved

OSS_to_GIC.Data[40]

reserved

OSS_to_GIC.Data[41]

reserved

OSS_to_GIC.Data[42]

reserved

OSS_to_GIC.Data[43]

reserved

OSS_to_GIC.Data[44]

reserved

OSS_to_GIC.Data[41]-->[127]

not used

GIC to OSS LIC bit assignments

Tag Name

Description

GIC_to_OSS

GIC_to_OSS.Connection_Status

GIC_to_OSS.Data[0]

GIC Emergency Stop is OK

GIC_to_OSS.Data[1]

GIC Fire Alarm is OK

GIC_to_OSS.Data[2]

GIC Seismic Alarm is OK

GIC_to_OSS.Data[3]

reserved

GIC_to_OSS.Data[4]

GIC reset

GIC_to_OSS.Data[5]

Light Path is blocked

GIC_to_OSS.Data[6]

reserved

GIC_to_OSS.Data[7]

reserved

GIC_to_OSS.Data[8]

Safety Shutter open permissive (0=shutter must close)

GIC_to_OSS.Data[9]

reserved

GIC_to_OSS.Data[10]

reserved

GIC_to_OSS.Data[11]

reserved

GIC_to_OSS.Data[12]

reserved

GIC_to_OSS.Data[13]

reserved

GIC_to_OSS.Data[14]

reserved

GIC_to_OSS.Data[15]

Reserved

GIC_to_OSS.Data[16]

reserved

GIC_to_OSS.Data[17]

reserved

GIC_to_OSS.Data[18]

reserved

GIC_to_OSS.Data[19]

reserved

GIC_to_OSS.Data[20]

reserved

GIC_to_OSS.Data[21]

reserved

GIC_to_OSS.Data[22]

reserved

GIC_to_OSS.Data[23]

reserved

GIC_to_OSS.Data[24]

reserved

GIC_to_OSS.Data[25]

reserved

GIC_to_OSS.Data[26]

reserved

GIC_to_OSS.Data[27]

reserved

GIC_to_OSS.Data[28]

reserved

GIC_to_OSS.Data[29]

reserved

GIC_to_OSS.Data[30]

reserved

GIC_to_OSS.Data[31]

reserved

GIC_to_OSS.Data[32]

reserved

GIC_to_OSS.Data[33]

reserved

GIC_to_OSS.Data[34]

reserved

GIC_to_OSS.Data[35]

reserved

GIC_to_OSS.Data[36]

reserved

GIC_to_OSS.Data[37]

reserved

GIC_to_OSS.Data[38]

reserved

GIC_to_OSS.Data[39]

reserved

GIC_to_OSS.Data[40]

reserved

GIC_to_OSS.Data[41]-->[127]

not used

Instrument LIC to GIC bit assignments

Tag Name

Description

INST_to_GIC

INST_to_GIC.Connection_Status

INST_to_GIC.Data[0]

Instruments Emergency Stop OK

INST_to_GIC.Data[1]

Instruments PLC I/O OK (LedStatus=3)

INST_to_GIC.Data[2]

Reserved

INST_to_GIC.Data[3]

Reserved

INST_to_GIC.Data[4]

Reserved

INST_to_GIC.Data[5]

Reserved

INST_to_GIC.Data[6]

Reserved

INST_to_GIC.Data[7]

Reserved

INST_to_GIC.Data[8]

Reserved

INST_to_GIC.Data[9]

Reserved

INST_to_GIC.Data[10]

Reserved

INST_to_GIC.Data[11]

Reserved

INST_to_GIC.Data[12]

Reserved

INST_to_GIC.Data[13]

Reserved

INST_to_GIC.Data[14]

Reserved

INST_to_GIC.Data[15]

Reserved

INST_to_GIC.Data[16]

Reserved

INST_to_GIC.Data[17]

Reserved

INST_to_GIC.Data[18]

Reserved

INST_to_GIC.Data[19]

Reserved

INST_to_GIC.Data[20]

Reserved

INST_to_GIC.Data[21]

Reserved

INST_to_GIC.Data[22]

Reserved

INST_to_GIC.Data[23]

Reserved

INST_to_GIC.Data[24]

Reserved

INST_to_GIC.Data[25]

Reserved

INST_to_GIC.Data[26]

Reserved

INST_to_GIC.Data[27]

Reserved

INST_to_GIC.Data[28]

Reserved

INST_to_GIC.Data[29]

Reserved

INST_to_GIC.Data[30]

Reserved

INST_to_GIC.Data[31]

Reserved

INST_to_GIC.Data[32]

Reserved

INST_to_GIC.Data[33]

Reserved

INST_to_GIC.Data[34]

Reserved

INST_to_GIC.Data[35]

Reserved

INST_to_GIC.Data[36]

Reserved

INST_to_GIC.Data[37]

Reserved

INST_to_GIC.Data[38]

Reserved

INST_to_GIC.Data[39]

Reserved

INST_to_GIC.Data[40]

Reserved

INST_to_GIC.Data[41]

Reserved

INST_to_GIC.Data[42]

Reserved

INST_to_GIC.Data[43]

Reserved

INST_to_GIC.Data[44]

Reserved

INST_to_GIC.Data[41]-->[127]

not used

 