PLC 4 Download Checklist:

Download means PC => PLC (D is for Danger!)

PLC 4 is located on the Utility Level S&O

  • Is the air knife open? It will close!

  • All pumps will stop

  • Pump VFD’s network connections will need reset via HMI

  • Check PLC4 Cabinet for bad network I/O

  • Weather stations will stop reporting

  • Water bugs will likely trip and send alarms

  • If TSW is running, it will stop causing Heat Stop Safety shutter to close

  • Check than TCM (16°C) is off, after download, there may be a false positivie that it is running. Press the update button to refresh status.

Info

PLC 5 Download Checklist:

Download means PC => PLC. (D is for Danger!)

PLC 5 is located on the Ground Floor Utility Building

Cooling will stop during a download!

  • All pumps will stop

  • Chillers should be off BEFORE download

  • Water treatment may need reset

    • Auto Duty Cycle for pumps will default to off, turn on via Water Treatment page on Utilities HMI Project

...