Versions Compared

Key

  • This line was added.
  • This line was removed.
  • Formatting was changed.

...

Trigger

Message

Recovery

{[TEL]TMAAlt_SpeedLimitOK_DCM.O1}==0

Telescope Altitude Overspeed

Telescope Altitude Axis has exceeded the maximum allowable speed.

  1. Investigate cause.

  2. GIS reset.

{[TEL]TMAAlt_SS1StopRampOK_DCM.O1}==0

Telescope Altitude Stop Ramp Violation

Telescope Altitude Axis did not decelerate as expected during a Safe Stop 1 event.

  1. Investigate cause of Safe Stop 1 trigger.

  2. Investigate cause of failure to decelerate.

  3. Reset Telescope Altitude Axis encoder.

  4. GIS reset.

{[TEL]TMAAz_SpeedLimitOK_DCM.O1}==0

Telescope Azimuth Overspeed

Telescope Azimuth Axis has exceeded the maximum allowable speed.

  1. Investigate cause.

  2. GIS reset.

{[TEL]TMAAz_SS1StopRampOK_DCM.O1}==0

Telescope Azimuth Stop Ramp Violation

Telescope Azimuth Axis did not decelerate as expected during a Safe Stop 1 event.

  1. Investigate cause of Safe Stop 1 trigger.

  2. Investigate cause of failure to decelerate.

  3. Reset Telescope Azimuth Axis encoder.

  4. GIS reset.

{[TEL]TMAAz_UpperFinalLimits_DCM.O1}==0

Telescope Azimuth Upper Final Limit Exceeded

Telescope Azimuth Axis upper final limit has been exceeded.

  1. Investigate cause.

  2. Telescope end-of-travel limit possibly needs reset as well.

  3. Manual move telescope out of limit.

  4. Reset GIS.

{[TEL]TMAAz_LowerFinalLimits_DCM}==0

Telescope Azimuth Lower Final Limit Exceeded

Telescope Azimuth Axis lower final limit has been exceeded.

  1. Investigate cause.

  2. Telescope end-of-travel limit possibly needs reset as well.

  3. Manual move telescope out of limit.

  4. Reset GIS.

{[TEL]TMAAlt_UpperFinalLimits_DCM}==0

Telescope Altitude Upper Final Limit Exceeded

Telescope Altitude Axis upper final limit has been exceeded.

  1. Investigate cause.

  2. Manual move telescope out of limit.

  3. Reset GIS.

{[TEL]TMAAlt_LowerFinalLimits_DCM}==0

Telescope Altitude Lower Final Limit Exceeded

Telescope Altitude Axis lower final limit has been exceeded.

  1. Investigate cause.

  2. Manual move telescope out of limit.

  3. Reset GIS.

{[ROT]ROTO_EStop_Internal_OK}==0

Coudé Rotator Emergency Stop

One of the Emergency Stop devices connected to the Coudé LIC has been activated or has faulted. An additional alarm should be present that indicates which Emergency Stop device is the source.

Possible sources are:

  • one of ten possible emergency stop push buttons located around the Coudé rotator

  • the hand-held device (HHD) connected to one of seven HHD connection boxes

{[ROT]ROTO_Estop_HHD_Box_CHHD_CPL_DCST_OK}==0

Coudé Platform Left E-Stop Button Pressed

The emergency stop push button located on the left Coudé Platform HHD connection box has been activated or has faulted.

  1. Determine cause.

  2. Reset Emergency Stop Device by rotating switch counter-clockwise.

  3. GIS Reset.

{[ROT]ROTO_Estop_HHD_Box_CHHD_CPR_DCST_OK}==0

Coudé Platform Right E-Stop Button Pressed

{[ROT]ROTO_Estop_HHD_Box_CHHD_CR_DCST_OK}==0

Coudé Room E-Stop Button Pressed

{[ROT]ROTO_Estop_HHD_Box_CHHD_MLL_DCST_OK}==0

Mezzanine Left E-Stop Button Pressed

{[ROT]ROTO_Estop_HHD_Box_CHHD_MLR_DCST_OK}==0

Mezzanine Right E-Stop Button Pressed

{[ROT]ROTO_Estop_HHD_Box_CHHD_CWO_DCST_OK}==0

Coudé Cable Wrap Outer E-Stop Button Pressed

{[ROT]ROTO_Estop_HHD_CHHD_CWI_DCST_OK}==0

Coudé Cable Wrap Inner E-Stop Button Pressed

{[ROT]ROTO_Estop_Rope_CR_ML_DCST_OK}==0

Coudé Cable Wrap Rope Pull E-Stop Cable Pulled

{[ROT]ROTO_Estop_CHS1_JB_DCST_OK}==0

Coudé Cable Wrap Inner CHS1-JB E-Stop Button Pressed

{[ROT]ROTO_Estop_CHS2_JB_DCST_OK}==0

Coudé Cable Wrap Inner CHS2-JB E-Stop Button Pressed

{[ROT]ROTO_Estop_HHD_CHHD_CPR_DCST_OK}==0

Coudé Platform Right HHD E-Stop Button Pressed

{[ROT]ROTO_Estop_HHD_CHHD_CPL_DCST_OK}==0

Coudé Platform Left HHD E-Stop Button Pressed

{[ROT]ROTO_Estop_HHD_CHHD_CR_DCST_OK}==0

Coudé Room HHD E-Stop Button Pressed

{[ROT]ROTO_Estop_HHD_CHHD_MLL_DCST_OK}==0

Mezzanine Left HHD E-Stop Button Pressed

{[ROT]ROTO_Estop_HHD_CHHD_MLR_DCST_OK}==0

Mezzanine Right HHD E-Stop Button Pressed

{[ROT]ROTO_Estop_HHD_CHHD_CWO_DCST_OK}==0

Coudé Cable Wrap Outer HHD E-Stop Button Pressed

{[ENC]Enc_ESTOP401_OK}==0

Enclosure E-Stop 401 Pressed

{[ENC]Enc_ESTOP402_OK}==0

Enclosure E-Stop 402 Pressed

{[ENC]Enc_ESTOP403_OK}==0

Enclosure E-Stop 403 Pressed

{[ENC]Enc_ESTOP404_OK}==0

Enclosure E-Stop 404 Pressed

{[ENC]Enc_ESTOP501_OK}==0

Enclosure E-Stop 501 Pressed

{[ENC]Enc_ESTOP502}==0

Enclosure E-Stop 502 Pressed

{[ENC]Enc_ESTOP503_OK}==0

Enclosure E-Stop 503 Pressed

{[ENC]Enc_ESTOP504_OK}==0

Enclosure E-Stop 504 Pressed

{[ENC]Enc_ESTOP601_OK}==0

Enclosure E-Stop 601 Pressed

{[ENC]Enc_ESTOP602_OK}==0

Enclosure E-Stop 602 Pressed

{[ENC]Enc_ESTOP201_OK}==0

Enclosure E-Stop 201 Pressed

{[ENC]Enc_ESTOP202_OK}==0

Enclosure E-Stop 202 Pressed

{[ENC]Enc_ESTOP301_OK}==0

Enclosure E-Stop 301 Pressed

{[ENC]Enc_ESTOP302_OK}==0

Enclosure E-Stop 302 Pressed

{[ENC]Enc_ESTOP303_OK}==0

Enclosure E-Stop 303 Pressed

{[ENC]Enc_ESTOP304_OK}==0

Enclosure E-Stop 304 Pressed

{[ENC]Enc_ESTOP305_OK}==0

Enclosure E-Stop 305 Pressed

{[ENC]Enc_ESTOP_Pendant}==0

Enclosure HMI Pendant E-Stop Pressed

{[ENC]Enc_ESTOP702_OK}==0

Enclosure E-Stop 701 Pressed

{[ENC]Enc_ESTOP801_OK}==0

Enclosure E-Stop 801 Pressed

{[ENC]Enc_ESTOP901_OK}==0

Enclosure E-Stop 901 Pressed

{[TEL]TMO_EStop_HHD_Box_MHHD_TPL_DCST_OK}==0

Overall E-Stop Pushbutton Mount HHD Box Telescope Platform Left E-Stop Button Pressed

{[TEL]TMO_EStop_HHD_Box_MHHD_TPR_DCST_OK}==0

Overall E-Stop Pushbutton Mount HHD Box Telescope Platform Right E-Stop Button Pressed

{[TEL]TMO_EStop_HHD_Box_MHHD_NPL_DCST_OK}==0

Overall E-Stop Pushbutton Mount HHD Box Nasmyth Platform Left E-Stop Button Pressed

{[TEL]TMO_EStop_HHD_Box_MHHD_NPR_DCST_OK}==0

Overall E-Stop Pushbutton Mount HHD Box Nasmyth Platform Right E-Stop Button Pressed

{[TEL]TMO_EStop_HHD_Box_MHHD_SRL_DCST_OK}==0

Overall E-Stop Pushbutton Mount HHD Box Service Ring Left E-Stop Button Pressed

{[TEL]TMO_EStop_HHD_Box_MHHD_SRR_DCST_OK}==0

Overall E-Stop Pushbutton Mount HHD Box Service Ring Right  E-Stop Button Pressed

{[TEL]TMO_EStop_Mount_Rope_DCST_OK}==0

Telescope Mount Overall E-Stop Rope Switch E-Stop Cable Pulled

{[TEL]TMO_Estop_HHD_Box_MHHD_CWO_DCST_OK}==0

Telescope Mount Overall E-Stop Pushbutton Mount HHD Box Cable Wrap Outer E-Stop Button Pressed

{[TEL]TMO_EStop_HHD_Box_MHHD_CWI_DCST_OK}==0

Telescope Mount Overall E-Stop Pushbutton Mount HHD Box Cable Wrap Inner E-Stop Button Pressed

{[TEL]TMO_EStop_OSSPlatformLeft_DCST_OK}==0

Telescope Mount Overall E-Stop Pushbutton OSS Platfrom Left E-Stop Button Pressed

{[TEL]TMO_EStop_OSSPlatformRight_DCST_OK}==0

Telescope Mount Overall E-Stop Pushbutton OSS Platfrom Right  E-Stop Button Pressed

{[TEL]TMO_EStop_MirrorCoverContrlPanel_DCST_OK}==0

Telescope Mount Overall E-Stop Pushbutton M1 Mirror Cover Control Panel E-Stop Button Pressed

{[TEL]TMO_EStop_Bridge1_CP_MAZ_B1CP_DCST_OK}==0

Telescope Mount Overall E-Stop Pushbutton Bridge 1 Control Panel E-Stop Button Pressed

{[TEL]TMO_EStop_Bridge2_CP_MAZ_B2CP_DCST_OK}==0

Telescope Mount Overall E-Stop Pushbutton Bridge 2 Control Panel E-Stop Button Pressed

{[TEL]TMAAz_MHHD_Estop_HHD_TPL_DCST_OK}==0

Azimuth Axis Telescope Platform Left HHD E-Stop Button Pressed

{[TEL]TMAAlt_MHHD_Estop_HHD_TPL_DCST_OK}==0

Altitude Axis Telescope Platform Left HHD E-Stop Button Pressed

{[TEL]TMAAz_MHHD_Estop_HHD_TPR_DCST_OK}==0

Azimuth Axis Telescope Platform Right HHD E-Stop Button Pressed

{[TEL]TMAAlt_MHHD_Estop_HHD_TPR_DCST_OK}==0

Altitude Axis Telescope Platform Right HHD E-Stop Button Pressed

{[TEL]TMAAz_MHHD_Estop_HHD_NPL_DCST_OK}==0

Azimuth Axis Nasmyth Platform Left HHD E-Stop Button Pressed

{[TEL]TMAAlt_MHHD_Estop_HHD_NPL_DCST_OK}==0

Altitude Axis Nasmyth Platform Left HHD E-Stop Button Pressed

{[TEL]TMAAz_MHHD_Estop_HHD_NPR_DCST_OK}==0

Azimuth Axis Nasmyth Platform Right HHD E-Stop Button Pressed

{[TEL]TMAAlt_MHHD_Estop_HHD_NPR_DCST_OK}==0

Telescope Mount Altitude Axis Nasmyth Platform Right HHD E-Stop Button Pressed

{[TEL]TMO_EStop_HHD_MHHD_SRL_DCST_OK}==0

Telescope Mount Overall E-Stop Pushbutton Mount HHD Box Service Ring Left E-Stop Button Pressed

{[TEL]TMO_EStop_HHD_MHHD_SRR_DCST_OK}==0

Telescope Mount Overall E-Stop Pushbutton Mount HHD Box Service Ring Right E-Stop Button Pressed

{[TEL]TMO_EStop_HHD_MHHD_CWO_DCST_OK}==0

Telescope Mount Overall E-Stop Pushbutton Mount HHD Box Cable Wrap Outer E-Stop Button Pressed

{[TEL]TMO_EStop_HHD_MHHD_CWI_DCST_OK}==0

Telescope Mount Overall E-Stop Pushbutton Mount HHD Box Cable Wrap Inner E-Stop Button Pressed

{[GIC]@IsPresent}==0

GIC connection is not present

GIC processor is not availableon-line and contains a program.

Possible causes:

  • Network failure

  • Controller failure

    • controller not running

    • no program loaded

{[TEL]@IsPresent}==0

Telescope LIC is not present

Telescope LIC is not available.

{[FAC]FAC_EStop_ControlRoom_OK}==0

Control Room Emergency Stop Pressed

({[GIC]OSS_HeatStop_PressureOK}==0) AND ({[GIC]LightPath_Blocked}==0)

Heat Stop Pressure too low

Coolant pressure to the heat stop is too low.

{[GIC]OSS_HeatStop_TemperatureOK}==0 AND ({[GIC]LightPath_Blocked}==0)

Heat Stop Temperature too high

Coolant temperature to the heat stop is too high.

{[GIC]SafetyShutter_CloseFault}==1

Safety Shutter failed to close

The safety shutter was commanded to close but failed to do so in the expected time.

{[GIC]M1Cover_CloseFault}==1

M1 Cover failed to close

M1 Cover was commanded to close but failed to do so in the expected time.

{[GIC]GIC_SafetyShutter_CmdClose}

GIC commanded Safety Shutter to close

The safety shutter has been commanded to close by the GIS.

{[GIC]GIC_M1Cover_CmdClose}

GIC commanded M1 Cover to close

The M1 cover has been commanded to close by the GIS.

{[GIC]GIC_ApCover_CmdClose}

GIC commanded Aperture Cover to close

The Aperture Cover has been commanded to close by the GIS.

{[GIC]ApCover_CloseFault}

Aperture Cover failed to close

The Aperture Cover was commanded to close but failed to do so in the expected time.

{[GIC]FAC_SeismicSensor1_DCS.O1}==0

Seismic Activity Detected (sensor 1)

{[GIC]FAC_SeismicSensor2_DCS.O1}==0

Seismic Activity Detected (sensor 2)

{[ROT]ROTAAz_Speed_Limit_OK}==0

Coude Speed Limit Violation

{[ROT]ROTAAz_Upper_Final_Limit_OK}==0

Coude Rotator Upper Final Limit Exceeded

{[ROT]ROTAAz_Lower_Final_Limit_OK}==0

Coude Rotator Lower Final Limit Exceeded

{[ROT]ROTAAz_Hard_Stops_OK}==0

Coude Rotator Hard Stops are not OK

{[ROT]ROTAAz_CableWrapLowerAlignment_OK}==0

Coude Rotator Cable Wrap Mis-alignment (lower)

{[ROT]ROTAAz_CableWrapUpperAlignment_OK}==0

Coude Rotator Cable Wrap Mis-alignment (upper)

{[ENC]EncLIC_EStop406_OK}==0

Enclosure E-Stop 406 Pressed

{[GIC]PowerSupply_Failure}

Redundant Power Supply Failure in GIC cabinet

One of the redundant power supplies in the GIC cabinet has failed.

Repair or replace power supply as soon as practical.

{[GIC]GIC_FireAlarm_OK}==0

Facilities Fire Alarm Activated. Evacuate Immediately.{[GIC]REP_OK}==0

Why are you reading this? The building is on fire!

  1. Get out!!!

  2. After you are sure there is no fire. Reset FACP.

  3. Reset GIS

{[GIC]REP_OK}==0

Redundant Ethernet Ring Failure. Check network connections.

There is a failure within the safety network’s redundant ethernet ring.

Investigate and repair as soon as practical.

{[TEL]Azimuth_SFX.SFH}==0

Telescope Azimuth Safety Encoder not homed

The Telescope Azimuth AB safety encoder has not been homed.

  1. Home telescope safety encoder.

({[GIC]FOV_Configuration_OK} OR {[GIC]LightPath_Blocked})==0

Wrong Field-of-View Selected

{[TEL]Altitude_SFX.SFH}==0

Telescope Altitude Safety Encoder not homed

An inconsistent instrument configuration has been selected.

Configure the GOS and instrument to an acceptable configuration.

  • Cryo-NIRSP Large FOV

    • GOS 5 arcminute

    • M9A deployed

    • DLFM1 stowed

  • Cryo-NIRSP Small FOV

    • GOS 2.8 arcminute

    • M9A deployed

    • DLFM1 stowed

  • Small FOV

    • GOS 2.8 arcminute

    • M9A Stowed

    • DLFM1 stowed

{[TEL]Altitude_SFX.SFH}==0

Telescope Altitude Safety Encoder not homed

The Telescope Altitude AB safety encoder has not been homed.

  1. Home telescope safety encoder.

{[OSS]HeatStop_Fuse_Wire_Alarm_OK}==0==0

Heat Stop Fuse Wire melted

The Heat Stop Fuse Wire has melted.

  1. Replace Heat Stop Fuse Wire

melted
  1. .

{[OSS]HeatStop_Fuse_Wire_Fault_OK}==0

Heat Stop Fuse Wire faulted

{[OSS]HeatStop_OverTemp12_OK}==0

Heat Stop Overtemp 1 & 2

{[OSS]HeatStop_OverTemp34_OK}==0

Heat Stop Overtemp 3 & 4

{[OSS]M5_Temperature_OK}==0

M5 Overtemp

({[GIC]OSS_HeatStop_ShutterOpen}  OR  {[GIC]LightPath_Blocked})==0

Safety Shutter not fully open

Safety shutter was not fully opened while concentrated light was present.

  1. Fully open safety shutter.

  2. Reset GIS.

{[OSS]HeatAbsorber_OverTemp56_OK}==0

Heat Absorber Overtemp 5&6 

{[OSS]HeatAbsorber_OverTemp78_OK}==0

Heat Absorber Overtemp 7&8

{[Tel]GrandMasterClock_IsLocked}==0

Grand Master Clock in not locked

The Telescope LIC PTP clock is no longer synced to the Grandmaster clock.

  1. Investigate PTP clock system.

{[Tel]GrandMasterClock_InHoldover}==1

Grand Master Clock in holdover

The Telescope LIC PTP clock is no longer synced to the Grandmaster clock but is still with tolerance.

  1. Investigate PTP clock system as soon as practical.