2022-02-24

SB-UPSL4B

EGS

M3/M4/M6 feed optics thermal rack circuit changed from 1P-120V to 2P-208V due to overcurrent condition with original circuit and ePDU. Branch circuit moved from SB-UPSL4B-25 to new 30A breaker on 22,24. Details in TOE-145.

View file
nameSB-UPSL4B FOTR feeder change to 2P-30A.pdf