If you would like to report an HMI bug or would like to request a new feature you can do so via TOE-152:

Jira Legacy
serverSystem JIRAJira
serverIdb9f64e64-1a61-3bf5-b3ac-d97674e9bd1d
keyTOE-152
(Old)

Jira Legacy
serverSystem JIRAJira
serverIdb9f64e64-1a61-3bf5-b3ac-d97674e9bd1d
keyTOE-424
(Old)

Jira Legacy
serverSystem Jira
serverIdb9f64e64-1a61-3bf5-b3ac-d97674e9bd1d
keyTOE-598

Server Info:

OCP Notes:

https://docs.google.com/spreadsheets/d/1z5rZzV-nd4Ef7W3E6pv4-MIUYVDHkq4ZaIlrDuL0B7E/edit?usp=sharing

...

-Due to the Chillers being off for an extended period, we had to wait 24 hrs to turn them on to let the crankcase heaters operate. In order to start cryo cooling in the meantime, we turned off valves to the server rm and burned ice on the CHW loop with a setpoint of 55. We then turned on TAC with a setpoint of 65°F. This resulted in a burn rate of about 2% per hour and allowed cooling overnight. Ambient temperatures were also cold, which was likely advantageous.

https://www.dropbox.com/scl/fi/b0qhhjai0wzhsbenu7q1h/OPC2.5-Thermal-Eng-Guide.pdf?rlkey=bhb2nby0fra7qrbjl6baes4jc&dl=0

...

https://www.dropbox.com/s/p8wug0xrvv6wose/OCP1.6%20FMS%20HMI%20Overview.mp4?dl=0

...

View file
nameActive Ventilation Operation.pdf
View file
nameWind Alarm Inhibit.pdf
View file
nameWater Treatment System.pdf
View file
nameMotionHazardDisplay.pdf
View file
nameHMI Download Instructions.pdf
View file
nameFMS startup procedure.pdf
View file
nameFMS shutdown procedure.pdf
View file
nameAlarms Status and Journal.pdf
View file
nameAlarm Update and Reply.pdf
View file
nameMotionHazardDisplay.pdf

View file
nameActive Ventilation Operation.pdf

PLC Notes:

Contact Chris Foster for PLC code changes or download requests.

Info

PLC 4 Download Checklist:

Download means PC => PLC (D is for Danger!)

PLC 4 is located on the Utility Level S&O

  • Is the air knife open? It will close!

  • All pumps will stop

  • Pump VFD’s network connections will need reset via HMI

  • Check PLC4 Cabinet for bad network I/O

  • Weather stations will stop reporting

  • Water bugs will likely trip and send alarms

  • If TSW is running, it will stop causing Heat Stop Safety shutter to close

  • Check than TCM (16°C) is off, after download, there may be a false positivie that it is running. Press the update button to refresh status.

Info

PLC 5 Download Checklist:

Download means PC => PLC. (D is for Danger!)

PLC 5 is located on the Ground Floor Utility Building

Cooling will stop during a download!

  • All pumps will stop

  • Chillers should be off BEFORE download

  • Water treatment may need reset

    • Auto Duty Cycle for pumps will default to off, turn on via Water Treatment page on Utilities HMI Project

Aug 2023 Power Issues

CH03 voltage monitor tripping on under voltage each time the last compressor fires up:

Monitor settings:

Adjusted CH02/03/05 voltage monitors:

%under 5 → 7

%over 5 → 7

fault delay sec 6 → 10

Avg Volt 489 → 480

Chart before adjustments (each spike is when voltage monitors were tripping:

...

Measured CH05 Circuits 1 and 2 amps with clamp meter compared to chiller readout. Chiller reading low on both by about .4 amps.