Overspeed Reset
The mount and Coudé main axis have their speed monitored by the Kuebler Safety Encoders. While it should not be possible to command speeds greater than allowable limits it is possible that the Overspeed Monitoring may be tripped.
When this happens the Kuebler must be reset prior to resuming operations. This should be possible using the HMI engineering screen. On the right side there is a button that indicates that a reset is required and also serves as the reset button.
To reset the safety encoder manually access the GIS subrack in cabinet CCC located the Coude ‘Rec Room’. The button is located just above the 7-segement LED. The button is labeled as ‘Function.’ Using the Kuebler Betätigungsstift Set-Taste or other suitable actuator, such as a pen.
Do not use a pencil as the tip may break off and jam the button.
After pressing the reset button and successfully resetting the safety encoder the 7-segment display will show '4' which indicates the safety encoder is working properly.
The GIS will also need to be reset via one of the HMI (either utility level or control room).
Encoder Faulted
If the Kuebler safety encoder goes into alarm or fault it will cause multiple interlocks to be tripped, including: both final limits faulted, Hard Stops not OK, Speed Limit Exceeded, and Stop Ramp violation as shown below.
The process to reset the Kuebler should be the same as above.