Procedure to download and activate modified code on Beckhoff PLC

Skip to end of metadata
Go to start of metadata

You are viewing an old version of this page. View the current version.

Compare with Current View Page History

« Previous Version 4 Next »

Beckhoff code development and modification happens on two applications:

  • TwinCAT PLC Control
    This is the IDE for code development. Code projects are opened as *.pro file and editing is allowed in any of the standard IEC-61131 languages (Structured Text, Ladder Logic etc.). Compiling and downloading to PLC runtime is also done from here.

  • TwinCAT System Manager
    This is the tool for configuring hardware and linking code variables to I/O terminals.

Over time we have converged to a reliable way to download code to Beckhoff PLC (local or remote runtimes). The key steps are listed below:

  1. Clean Project
    After performing necessary modifications to project in TwinCAT PLC Control click Project → Clean All. This command executes the cleanup process which deletes the compile information (compile log) that enables online change. After cleanup online change is not possible without a full rebuild and download. The command pops up a series of dialog boxes to lead through the process



    It’s always a good idea to perform a clean rebuild and download after code modification. On the second popup asking to leave Configuration unchanged only press ‘Yes’ if no variables are to be linked to hardware. Pressing ‘Yes’ breaks the hardware configuration and requires code rescan in System Manager.

  2. Compile Project
    Click Project → Rebuild All. This command compiles all the components of the project including the new changes. The results window shows the compile results (shown below for the case where we pressed ‘Yes’).


    Notice the warning indicating missing VAR_CONFIG. This indicates the need to rescan and reactivate project on the PLC using System Manager.

  3. Rescan Project
    The rescan operation happens in the System Manager. Launch System Manager and open the file currently linked to the project in question. Navigate to the project under ‘PLC - Configuration’ in the explorer window and click the ‘Rescan’ button.

At this point it’s a good idea to confirm that the rescan didn’t disturb your existing hardware links. In the figure below the hardware links are indicated by the small arrows next to the hardware I/O terminal.