This section is based on TN-0157 GIS Programming. This Tech Note contain configuration details and programming styles that were not an absolute requirement or specification. It was to layout guidelines for GIS programming to promote consistency.
The reason this is a Tech Note rather than a Spec was that specifications were also contract requirements. Changing contractual requirements after the contract was signed was an onerous process so using a technical note to detail configuration information was the route chosen.
Network Configuration
Stratix 8300 switch address are configured as follows:
System | Address | Hostname |
Global Interlock Controller | 10.4.0.1 | GIS_Switch |
Telescope Mount Drive Assembly | 10.4.0.201 | Tel_Switch |
Coudé Rotator System | 10.4.0.202 | Rot_Switch |
Optical Support System | 10.4.0.203 | OSS_Switch |
Instruments System | 10.4.0.204 | Inst_Switch |
Enclosure (lower) | 10.4.0.205 | Enc_Switch |
Facility | 10.4.0.206 | Fac_Switch |
Facility Thermal System | 10.4.0.207 | FTS_Switch |
Enclosure (upper) | 10.4.0.209 | Enc_Switch2 |
Virtual LANs (VLANs) are configured as follows:
System | VLAN Name | VLAN ID | Address Space |
Global Interlock Controller | VLAN0100 | 100 | 10.4.0.0/24 |
Telescope Mount Drive Assembly | VLAN0101 | 101 | 10.4.1.0/24 |
Coudé Rotator System | VLAN0102 | 102 | 10.4.2.0/24 |
Optical Support System | VLAN0103 | 103 | 10.4.3.0/24 |
Instruments System | VLAN0104 | 104 | 10.4.4.0/24 |
Enclosure | VLAN0105 | 105 | 10.4.5.0/24 |
Facility Equipment | VLAN0106 | 106 | 10.4.6.0/24 |
Facility Thermal System | VLAN0107 | 107 | 10.4.7.0/24 |
Development LIC1 | VLAN0108 | 108 | 10.4.8.0/24 |
Development LIC2 | VLAN0109 | 109 | 10.4.9.0/24 |
Setup | VLAN0192 | 192 | 192.168.0.0/16 |
IP Addressing
GIC to LIC communications
Communications between the GIC and the LIC consist of tag of the user-defined type UDT_SafetyArray. This is essentially an array of 128 bits plus CONNECTION_STATUS.
User Defined Type UDT_SafetyArray
GIC to Enclosure bit assignments
Tag Name | Description |
GIC_to_ENC | |
GIC_to_ENC.Connection_Status | |
GIC_to_ENC.Data[0] | Global Emergency Stop OK |
GIC_to_ENC.Data[1] | Fire Alarm OK |
GIC_to_ENC.Data[2] | Seismic Alarm OK |
GIC_to_ENC.Data[3] | reserved |
GIC_to_ENC.Data[4] | Reset Command from GIC |
GIC_to_ENC.Data[5] | reserved |
GIC_to_ENC.Data[6] | reserved |
GIC_to_ENC.Data[7] | reserved |
GIC_to_ENC.Data[8] | Inner Pier Hazardous Zone Locked |
GIC_to_ENC.Data[9] | Mezzanine Level Hazardous Zone Locked |
GIC_to_ENC.Data[10] | Coudé Lab Hazardous Zone Locked |
GIC_to_ENC.Data[11] | Utility Level Hazardous Zone Locked |
GIC_to_ENC.Data[12] | Catwalk Hazardous Zone Locked |
GIC_to_ENC.Data[13] | Service Ring Hazardous Zone Locked |
GIC_to_ENC.Data[14] | Enclosure Floor Hazardous Zone Locked |
GIC_to_ENC.Data[15] | Telescope Hazardous Zone Locked |
GIC_to_ENC.Data[16] | Upper Enclosure Hazardous Zone Locked |
GIC_to_ENC.Data[17] | reserved |
GIC_to_ENC.Data[18] | reserved |
GIC_to_ENC.Data[19] | reserved |
GIC_to_ENC.Data[20] | Enclosure Azimuth OK to move |
GIC_to_ENC.Data[21] | Enclosure Azimuth Full Speed OK |
GIC_to_ENC.Data[22] | reserved |
GIC_to_ENC.Data[23] | reserved |
GIC_to_ENC.Data[24] | Enclosure Altitude OK to move |
GIC_to_ENC.Data[25] | reserved |
GIC_to_ENC.Data[26] | reserved |
GIC_to_ENC.Data[27] | reserved |
GIC_to_ENC.Data[28] | Aperture Cover OK to move |
GIC_to_ENC.Data[29] | Aperture Cover OK to open |
GIC_to_ENC.Data[30] | reserved |
GIC_to_ENC.Data[31] | reserved |
GIC_to_ENC.Data[32] | Bridge Crane OK to move |
GIC_to_ENC.Data[33] | reserved |
GIC_to_ENC.Data[34] | reserved |
GIC_to_ENC.Data[35] | reserved |
GIC_to_ENC.Data[36] | Jib Crane OK to move |
GIC_to_ENC.Data[37] | reserved |
GIC_to_ENC.Data[38] | reserved |
GIC_to_ENC.Data[39] | reserved |
GIC_to_ENC.Data[40] | Rear Door OK to move |
GIC_to_ENC.Data[41] | Rear Door OK to open |
GIC_to_ENC.Data[42] | reserved |
GIC_to_ENC.Data[43] | reserved |
GIC_to_ENC.Data[44]-->[127] | not used |
Enclosure to GIC bit assignments
Tag Name | Description |
ENC_to_ENC | |
ENC_to_GIC.Connection_Status | |
ENC_to_GIC.Data[0] | Enclosure Emergency Stop OK |
ENC_to_GIC.Data[1] | Enclosure PLC I/O OK (LEDStatus=3) |
ENC_to_GIC.Data[2] | reserved |
ENC_to_GIC.Data[3] | reserved |
ENC_to_GIC.Data[4] | Enclosure Azimuth Ready |
ENC_to_GIC.Data[5] | Enclosure Altitude Ready |
ENC_to_GIC.Data[6] | Enclosure Lower Maintenance trapped key in place |
ENC_to_GIC.Data[7] | Enclosure Upper Maintenance trapped key in place |
ENC_to_GIC.Data[8] | Enclosure Azimuth Motion Stopped |
ENC_to_GIC.Data[9] | Enclosure Azimuth Safely Limited Speed |
ENC_to_GIC.Data[10] | Enclosure Azimuth CW Limit |
ENC_to_GIC.Data[11] | ReservedEnclosure Azimuth CCW Limit |
ENC_to_GIC.Data[12] | Enclosure Altitude Motion Stopped |
ENC_to_GIC.Data[13] | Enclosure Altitude local trapped key in place |
ENC_to_GIC.Data[14] | Enclosure Altitude Upper Limit |
ENC_to_GIC.Data[15] | Enclosure Altitude Lower Limit |
ENC_to_GIC.Data[16] | Aperture Cover Closed |
ENC_to_GIC.Data[17] | Aperture Cover local trapped key in place |
ENC_to_GIC.Data[18] | Aperture Cover Closed Limit |
ENC_to_GIC.Data[19] | Aperture Cover Open Limit |
ENC_to_GIC.Data[20] | Bridge Crane Stowed |
ENC_to_GIC.Data[21] | Bridge Crane local trapped key in place |
ENC_to_GIC.Data[22] | reserved |
ENC_to_GIC.Data[23] | reserved |
ENC_to_GIC.Data[24] | Jib Crane Stowed |
ENC_to_GIC.Data[25] | Jib Crane local trapped key in place |
ENC_to_GIC.Data[26] | reserved |
ENC_to_GIC.Data[27] | reserved |
ENC_to_GIC.Data[28] | TEOA Platform Stowed |
ENC_to_GIC.Data[29] | TEOA Platform local trapped key in place |
ENC_to_GIC.Data[30] | reserved |
ENC_to_GIC.Data[31] | reserved |
ENC_to_GIC.Data[32] | Enclosure Azimuth aligned with maintenance position |
ENC_to_GIC.Data[33] | Transfer Bridge Stowed |
ENC_to_GIC.Data[34] | Transfer Bridge Rails Stowed |
ENC_to_GIC.Data[35] | reserved |
ENC_to_GIC.Data[36] | Rear Door local trapped key in place |
ENC_to_GIC.Data[37] | reserved |
ENC_to_GIC.Data[38] | reserved |
ENC_to_GIC.Data[39] | reserved |
ENC_to_GIC.Data[40] | Altitude Cable Wrap Overtension OK |
ENC_to_GIC.Data[41] | Azimuth Cable Wrap Overtension OK |
ENC_to_GIC.Data[42] | reserved |
ENC_to_GIC.Data[43] | reserved |
ENC_to_GIC.Data[44] | reserved |
ENC_to_GIC.Data[41]-->[127] | not used |
GIC to Telescope LIC bit assignments
The table below is the proposed structure for GIC to Enclosure communications.
Tag Name | Description |
GIC_to_TEL | |
GIC_to_TEL.Connection_Status | |
GIC_to_TEL.Data[0] | Global Emergency Stop OK |
GIC_to_TEL.Data[1] | Fire Alarm OK |
GIC_to_TEL.Data[2] | Seismic Alarm OK |
GIC_to_TEL.Data[3] | reserved |
GIC_to_TEL.Data[4] | Reset Command from GIC |
GIC_to_TEL.Data[5] | reserved |
GIC_to_TEL.Data[6] | reserved |
GIC_to_TEL.Data[7] | reserved |
GIC_to_TEL.Data[8] | Inner Pier Hazardous Zone Locked |
GIC_to_TEL.Data[9] | Mezzanine Level Hazardous Zone Locked |
GIC_to_TEL.Data[10] | Coudé Lab Hazardous Zone Locked |
GIC_to_TEL.Data[11] | Utility Level Hazardous Zone Locked |
GIC_to_TEL.Data[12] | Catwalk Hazardous Zone Locked |
GIC_to_TEL.Data[13] | Service Ring Hazardous Zone Locked |
GIC_to_TEL.Data[14] | Enclosure Floor Hazardous Zone Locked |
GIC_to_TEL.Data[15] | Telescope Hazardous Zone Locked |
GIC_to_TEL.Data[16] | Upper Enclosure Hazardous Zone Locked |
GIC_to_TEL.Data[17] | reserved |
GIC_to_TEL.Data[18] | reserved |
GIC_to_TEL.Data[19] | reserved |
GIC_to_TEL.Data[20] | Telescope Azimuth OK to move |
GIC_to_TEL.Data[21] | Telescope Azimuth Full Speed OK |
GIC_to_TEL.Data[22] | reserved |
GIC_to_TEL.Data[23] | reserved |
GIC_to_TEL.Data[24] | Telescope Altitude OK to move |
GIC_to_TEL.Data[25] | Telescope Altitude Full Speed OK |
GIC_to_TEL.Data[26] | reserved |
GIC_to_TEL.Data[27] | reserved |
GIC_to_TEL.Data[28] | M1 Cover OK to move |
GIC_to_TEL.Data[29] | M1 Cover OK to open |
GIC_to_TEL.Data[30] | reserved |
GIC_to_TEL.Data[31] | reserved |
GIC_to_TEL.Data[32]-->[127] | not used |
Telescope to GIC bit assignments
Tag Name | Description |
TEL_to_GIC | |
TEL_to_GIC.Connection_Status | |
TEL_to_GIC.Data[0] | Telescope Mount Emergency Stop OK |
TEL_to_GIC.Data[1] | Telescope Mount PLC I/O OK (LedStatus=3) |
TEL_to_GIC.Data[2] | reserved |
TEL_to_GIC.Data[3] | reserved |
TEL_to_GIC.Data[4] | Telescope Mount Azimuth Ready |
TEL_to_GIC.Data[5] | Telescope Mount Altitude Ready |
TEL_to_GIC.Data[6] | Reserved |
TEL_to_GIC.Data[7] | Reserved |
TEL_to_GIC.Data[8] | Telescope Mount Azimuth Motion Stopped |
TEL_to_GIC.Data[9] | Telescope Mount Azimuth at Safe Speed |
TEL_to_GIC.Data[10] | Telescope Mount Azimuth CW Limit |
TEL_to_GIC.Data[11] | Telescope Mount Azimuth CCW Limit |
TEL_to_GIC.Data[12] | Telescope Mount Altitude Motion Stopped |
TEL_to_GIC.Data[13] | Telescope Mount Altitude at Safe Speed |
TEL_to_GIC.Data[14] | Telescope Mount Altitude Upper Limit |
TEL_to_GIC.Data[15] | Telescope Mount Altitude Lower Limit |
TEL_to_GIC.Data[16] | Reserved |
TEL_to_GIC.Data[17] | Reserved |
TEL_to_GIC.Data[18] | Reserved |
TEL_to_GIC.Data[19] | Reserved |
TEL_to_GIC.Data[20] | Telescope in M1 Maintenance Position Azimuth |
TEL_to_GIC.Data[21] | Telescope in M1 Maintenance Position Altitude |
TEL_to_GIC.Data[22] | Telescope in TEOA Maintenance Position Azimuth |
TEL_to_GIC.Data[23] | Telescope in TEOA Maintenance Position Altitude |
TEL_to_GIC.Data[24] | Reserved |
TEL_to_GIC.Data[25] | Reserved |
TEL_to_GIC.Data[26] | Reserved |
TEL_to_GIC.Data[27] | Reserved |
TEL_to_GIC.Data[28] | M1 Cover Closed |
TEL_to_GIC.Data[29] | M1 Cart Jacks Stowed |
TEL_to_GIC.Data[30] | M1 Cover permissive |
TEL_to_GIC.Data[31] | Reserved |
TEL_to_GIC.Data[32] | Telescope Altitude Hazardous Zones Locked |
TEL_to_GIC.Data[33] | Telescope Azimuth Hazardous Zones Locked |
TEL_to_GIC.Data[34] | Telescope Azimuth Cable Wrap Alignment OK |
TEL_to_GIC.Data[35] | Reserved |
TEL_to_GIC.Data[36] | OSS Bridge stowed |
TEL_to_GIC.Data[37] | OSS Bridge permissive |
TEL_to_GIC.Data[38] | M5 Bridge stowed |
TEL_to_GIC.Data[39] | M5 Bridge permissive |
TEL_to_GIC.Data[40] | Nasmyth Stairs Gates Closed |
TEL_to_GIC.Data[41] | Telescope Floor Y+/- Gates Closed |
TEL_to_GIC.Data[42] | Telescope Tower Doors Closed |
TEL_to_GIC.Data[43] | Telescope Floor Hatch Closed |
TEL_to_GIC.Data[44] | Reserved |
TEL_to_GIC.Data[45]-->[127] | not used |
GIC to Coudé Rotator LIC bit assignments
The table below is the proposed structure for GIC to Enclosure communications.
Tag Name | Description |
GIC_to_ROT | |
GIC_to_ROT.Connection_Status | |
GIC_to_ROT.Data[0] | Global Emergency Stop OK |
GIC_to_ROT.Data[1] | Fire Alarm OK |
GIC_to_ROT.Data[2] | Seismic Alarm OK |
GIC_to_ROT.Data[3] | Heartbeat |
GIC_to_ROT.Data[4] | Reset Command from GIC |
GIC_to_ROT.Data[5] | Reserved |
GIC_to_ROT.Data[6] | reserved |
GIC_to_ROT.Data[7] | reserved |
GIC_to_ROT.Data[8] | Inner Pier Hazardous Zone Locked |
GIC_to_ROT.Data[9] | Mezzanine Level Hazardous Zone Locked |
GIC_to_ROT.Data[10] | Coudé Lab Hazardous Zone Locked |
GIC_to_ROT.Data[11] | Utility Level Hazardous Zone Locked |
GIC_to_ROT.Data[12] | Catwalk Hazardous Zone Locked |
GIC_to_ROT.Data[13] | Service Ring Hazardous Zone Locked |
GIC_to_ROT.Data[14] | Enclosure Floor Hazardous Zone Locked |
GIC_to_ROT.Data[15] | Telescope Hazardous Zone Locked |
GIC_to_ROT.Data[16] | Upper Enclosure Hazardous Zone Locked |
GIC_to_ROT.Data[17] | reserved |
GIC_to_ROT.Data[18] | reserved |
GIC_to_ROT.Data[19] | reserved |
GIC_to_ROT.Data[20] | Coudé Azimuth OK to move |
GIC_to_ROT.Data[21] | Coudé Azimuth Full Speed OK |
GIC_to_ROT.Data[22] | reserved |
GIC_to_ROT.Data[23] | reserved |
GIC_to_ROT.Data[24]-->[127] | not used |
Coudé Rotator to GIC bit assignments
Tag Name | Description |
ROT_to_GIC | |
ROT_to_GIC.Connection_Status | |
ROT_to_GIC.Data[0] | Rotator Emergency Stop OK |
ROT_to_GIC.Data[1] | Rotator PLC I/O OK (LedStatus=3) |
ROT_to_GIC.Data[2] | reserved |
ROT_to_GIC.Data[3] | reserved |
ROT_to_GIC.Data[4] | Rotator Azimuth Ready |
ROT_to_GIC.Data[5] | reserved |
ROT_to_GIC.Data[6] | reserved |
ROT_to_GIC.Data[7] | reserved |
ROT_to_GIC.Data[8] | Rotator Motion Stopped |
ROT_to_GIC.Data[9] | Rotator at Safe Limited Speed |
ROT_to_GIC.Data[10] | Rotator CW Final Limit OK (0=in limit) |
ROT_to_GIC.Data[11] | Rotator CCW Limit OK (0=in limit) |
ROT_to_GIC.Data[12] | reserved |
ROT_to_GIC.Data[13] | reserved |
ROT_to_GIC.Data[14] | reserved |
ROT_to_GIC.Data[15] | reserved |
ROT_to_GIC.Data[16] | reserved |
ROT_to_GIC.Data[17] | reserved |
ROT_to_GIC.Data[18] | reserved |
ROT_to_GIC.Data[19] | reserved |
ROT_to_GIC.Data[20] | Rotator Cable Wrap Alignment OK |
ROT_to_GIC.Data[21] | reserved |
ROT_to_GIC.Data[22] | reserved |
ROT_to_GIC.Data[23] | reserved |
ROT_to_GIC.Data[24] | reserved |
ROT_to_GIC.Data[25] | reserved |
ROT_to_GIC.Data[26] | reserved |
ROT_to_GIC.Data[27] | reserved |
ROT_to_GIC.Data[28] | reserved |
ROT_to_GIC.Data[29] | reserved |
ROT_to_GIC.Data[30] | reserved |
ROT_to_GIC.Data[31] | reserved |
ROT_to_GIC.Data[32] | reserved |
ROT_to_GIC.Data[33] | reserved |
ROT_to_GIC.Data[34] | reserved |
ROT_to_GIC.Data[35] | reserved |
ROT_to_GIC.Data[36] | reserved |
ROT_to_GIC.Data[37] | reserved |
ROT_to_GIC.Data[38] | reserved |
ROT_to_GIC.Data[39] | reserved |
ROT_to_GIC.Data[40] | reserved |
ROT_to_GIC.Data[41]-->[127] | not used |
Optical Subsystem (OSS) to GIC bit assignments
Tag Name | Description |
OSS_to_GIC | |
OSS_to_GIC.Connection_Status | |
OSS_to_GIC.Data[0] | OSS Emergency Stop OK |
OSS_to_GIC.Data[1] | OSS PLC I/O OK (LedStatus=3) |
OSS_to_GIC.Data[2] | reserved |
OSS_to_GIC.Data[3] | reserved |
OSS_to_GIC.Data[4] | reserved |
OSS_to_GIC.Data[5] | reserved |
OSS_to_GIC.Data[6] | reserved |
OSS_to_GIC.Data[7] | reserved |
OSS_to_GIC.Data[8] | On Sun |
OSS_to_GIC.Data[9] | reserved |
OSS_to_GIC.Data[10] | reserved |
OSS_to_GIC.Data[11] | reserved |
OSS_to_GIC.Data[12] | reserved |
OSS_to_GIC.Data[13] | reserved |
OSS_to_GIC.Data[14] | reserved |
OSS_to_GIC.Data[15] | Reserved |
OSS_to_GIC.Data[16] | Heat Stop Shutter is fully open |
OSS_to_GIC.Data[17] | Heat Stop Shutter is fully closed |
OSS_to_GIC.Data[18] | Heat Stop Safety Shutter permissive |
OSS_to_GIC.Data[19] | Heat Stop Temperature is OK |
OSS_to_GIC.Data[20] | Heat Stop Coolant Pressure is OK |
OSS_to_GIC.Data[21] | Reserved |
OSS_to_GIC.Data[22] | Reserved |
OSS_to_GIC.Data[23] | Reserved |
OSS_to_GIC.Data[24] | Heat Stop is installed |
OSS_to_GIC.Data[25] | M2 is installed |
OSS_to_GIC.Data[26] | Reserved |
OSS_to_GIC.Data[27] | reserved |
OSS_to_GIC.Data[28] | reserved |
OSS_to_GIC.Data[29] | reserved |
OSS_to_GIC.Data[30] | reserved |
OSS_to_GIC.Data[31] | reserved |
OSS_to_GIC.Data[32] | M5 Temperature is OK. |
OSS_to_GIC.Data[33] | reserved |
OSS_to_GIC.Data[34] | reserved |
OSS_to_GIC.Data[35] | reserved |
OSS_to_GIC.Data[36] | reserved |
OSS_to_GIC.Data[37] | reserved |
OSS_to_GIC.Data[38] | reserved |
OSS_to_GIC.Data[39] | reserved |
OSS_to_GIC.Data[40] | reserved |
OSS_to_GIC.Data[41] | reserved |
OSS_to_GIC.Data[42] | reserved |
OSS_to_GIC.Data[43] | reserved |
OSS_to_GIC.Data[44] | reserved |
OSS_to_GIC.Data[41]-->[127] | not used |
GIC to OSS LIC bit assignments
Tag Name | Description |
GIC_to_OSS | |
GIC_to_OSS.Connection_Status | |
GIC_to_OSS.Data[0] | GIC Emergency Stop is OK |
GIC_to_OSS.Data[1] | GIC Fire Alarm is OK |
GIC_to_OSS.Data[2] | GIC Seismic Alarm is OK |
GIC_to_OSS.Data[3] | reserved |
GIC_to_OSS.Data[4] | GIC reset |
GIC_to_OSS.Data[5] | Light Path is blocked |
GIC_to_OSS.Data[6] | reserved |
GIC_to_OSS.Data[7] | reserved |
GIC_to_OSS.Data[8] | Safety Shutter open permissive (0=shutter must close) |
GIC_to_OSS.Data[9] | reserved |
GIC_to_OSS.Data[10] | reserved |
GIC_to_OSS.Data[11] | reserved |
GIC_to_OSS.Data[12] | reserved |
GIC_to_OSS.Data[13] | reserved |
GIC_to_OSS.Data[14] | reserved |
GIC_to_OSS.Data[15] | Reserved |
GIC_to_OSS.Data[16] | reserved |
GIC_to_OSS.Data[17] | reserved |
GIC_to_OSS.Data[18] | reserved |
GIC_to_OSS.Data[19] | reserved |
GIC_to_OSS.Data[20] | reserved |
GIC_to_OSS.Data[21] | reserved |
GIC_to_OSS.Data[22] | reserved |
GIC_to_OSS.Data[23] | reserved |
GIC_to_OSS.Data[24] | reserved |
GIC_to_OSS.Data[25] | reserved |
GIC_to_OSS.Data[26] | reserved |
GIC_to_OSS.Data[27] | reserved |
GIC_to_OSS.Data[28] | reserved |
GIC_to_OSS.Data[29] | reserved |
GIC_to_OSS.Data[30] | reserved |
GIC_to_OSS.Data[31] | reserved |
GIC_to_OSS.Data[32] | reserved |
GIC_to_OSS.Data[33] | reserved |
GIC_to_OSS.Data[34] | reserved |
GIC_to_OSS.Data[35] | reserved |
GIC_to_OSS.Data[36] | reserved |
GIC_to_OSS.Data[37] | reserved |
GIC_to_OSS.Data[38] | reserved |
GIC_to_OSS.Data[39] | reserved |
GIC_to_OSS.Data[40] | reserved |
GIC_to_OSS.Data[41]-->[127] | not used |
Instrument LIC to GIC bit assignments
Tag Name | Description |
INST_to_GIC | |
INST_to_GIC.Connection_Status | |
INST_to_GIC.Data[0] | Instruments Emergency Stop OK |
INST_to_GIC.Data[1] | Instruments PLC I/O OK (LedStatus=3) |
INST_to_GIC.Data[2] | Reserved |
INST_to_GIC.Data[3] | Reserved |
INST_to_GIC.Data[4] | Reserved |
INST_to_GIC.Data[5] | Reserved |
INST_to_GIC.Data[6] | Reserved |
INST_to_GIC.Data[7] | Reserved |
INST_to_GIC.Data[8] | Reserved |
INST_to_GIC.Data[9] | Reserved |
INST_to_GIC.Data[10] | Reserved |
INST_to_GIC.Data[11] | Reserved |
INST_to_GIC.Data[12] | Reserved |
INST_to_GIC.Data[13] | Reserved |
INST_to_GIC.Data[14] | Reserved |
INST_to_GIC.Data[15] | Reserved |
INST_to_GIC.Data[16] | Reserved |
INST_to_GIC.Data[17] | Reserved |
INST_to_GIC.Data[18] | Reserved |
INST_to_GIC.Data[19] | Reserved |
INST_to_GIC.Data[20] | Reserved |
INST_to_GIC.Data[21] | Reserved |
INST_to_GIC.Data[22] | Reserved |
INST_to_GIC.Data[23] | Reserved |
INST_to_GIC.Data[24] | Reserved |
INST_to_GIC.Data[25] | Reserved |
INST_to_GIC.Data[26] | Reserved |
INST_to_GIC.Data[27] | Reserved |
INST_to_GIC.Data[28] | Reserved |
INST_to_GIC.Data[29] | Reserved |
INST_to_GIC.Data[30] | Reserved |
INST_to_GIC.Data[31] | Reserved |
INST_to_GIC.Data[32] | Reserved |
INST_to_GIC.Data[33] | Reserved |
INST_to_GIC.Data[34] | Reserved |
INST_to_GIC.Data[35] | Reserved |
INST_to_GIC.Data[36] | Reserved |
INST_to_GIC.Data[37] | Reserved |
INST_to_GIC.Data[38] | Reserved |
INST_to_GIC.Data[39] | Reserved |
INST_to_GIC.Data[40] | Reserved |
INST_to_GIC.Data[41] | Reserved |
INST_to_GIC.Data[42] | Reserved |
INST_to_GIC.Data[43] | Reserved |
INST_to_GIC.Data[44] | Reserved |
INST_to_GIC.Data[41]-->[127] | not used |