• In progress
  • GIS GIC to LIC Communications

    This section is based on TN-0157 GIS Programming. This Tech Note contain configuration details and programming styles that were not an absolute requirement or specification. It was to layout guidelines for GIS programming to promote consistency.

    The reason this is a Tech Note rather than a Spec was that specifications were also contract requirements. Changing contractual requirements after the contract was signed was an onerous process so using a technical note to detail configuration information was the route chosen.

    GIC to LIC communications

    Communications between the GIC and the LIC consist of tag of the user-defined type UDT_SafetyArray. This is essentially an array of 128 bits plus CONNECTION_STATUS.

    User Defined Type UDT_SafetyArray

    GIC to Enclosure bit assignments

    Tag Name

    Description

    GIC_to_ENC

     

    GIC_to_ENC.Connection_Status

     

    GIC_to_ENC.Data[0]

    Global Emergency Stop OK

    GIC_to_ENC.Data[1]

    Fire Alarm OK

    GIC_to_ENC.Data[2]

    Seismic Alarm OK

    GIC_to_ENC.Data[3]

    reserved

    GIC_to_ENC.Data[4]

    Reset Command from GIC

    GIC_to_ENC.Data[5]

    reserved

    GIC_to_ENC.Data[6]

    reserved

    GIC_to_ENC.Data[7]

    reserved

    GIC_to_ENC.Data[8]

    Inner Pier Hazardous Zone Locked

    GIC_to_ENC.Data[9]

    Mezzanine Level  Hazardous Zone Locked

    GIC_to_ENC.Data[10]

    Coudé Lab Hazardous Zone Locked

    GIC_to_ENC.Data[11]

    Utility Level Hazardous Zone Locked

    GIC_to_ENC.Data[12]

    Catwalk Hazardous Zone Locked

    GIC_to_ENC.Data[13]

    Service Ring Hazardous Zone Locked

    GIC_to_ENC.Data[14]

    Enclosure Floor Hazardous Zone Locked

    GIC_to_ENC.Data[15]

    Telescope Hazardous Zone Locked

    GIC_to_ENC.Data[16]

    Upper Enclosure Hazardous Zone Locked

    GIC_to_ENC.Data[17]

    reserved

    GIC_to_ENC.Data[18]

    reserved

    GIC_to_ENC.Data[19]

    reserved

    GIC_to_ENC.Data[20]

    Enclosure Azimuth OK to move

    GIC_to_ENC.Data[21]

    Enclosure Azimuth Full Speed OK

    GIC_to_ENC.Data[22]

    reserved

    GIC_to_ENC.Data[23]

    reserved

    GIC_to_ENC.Data[24]

    Enclosure Altitude OK to move

    GIC_to_ENC.Data[25]

    reserved

    GIC_to_ENC.Data[26]

    reserved

    GIC_to_ENC.Data[27]

    reserved

    GIC_to_ENC.Data[28]

    Aperture Cover OK to move

    GIC_to_ENC.Data[29]

    Aperture Cover OK to open

    GIC_to_ENC.Data[30]

    reserved

    GIC_to_ENC.Data[31]

    reserved

    GIC_to_ENC.Data[32]

    Bridge Crane OK to move

    GIC_to_ENC.Data[33]

    reserved

    GIC_to_ENC.Data[34]

    reserved

    GIC_to_ENC.Data[35]

    reserved

    GIC_to_ENC.Data[36]

    Jib Crane OK to move

    GIC_to_ENC.Data[37]

    reserved

    GIC_to_ENC.Data[38]

    reserved

    GIC_to_ENC.Data[39]

    reserved

    GIC_to_ENC.Data[40]

    Rear Door OK to move

    GIC_to_ENC.Data[41]

    Rear Door OK to open

    GIC_to_ENC.Data[42]

    reserved

    GIC_to_ENC.Data[43]

    reserved

    GIC_to_ENC.Data[44]-->[127]

    not used

    Enclosure to GIC bit assignments

    Tag Name

    Description

    ENC_to_ENC

     

    ENC_to_GIC.Connection_Status

     

    ENC_to_GIC.Data[0]

    Enclosure Emergency Stop OK

    ENC_to_GIC.Data[1]

    Enclosure PLC I/O OK (LEDStatus=3)

    ENC_to_GIC.Data[2]

    reserved

    ENC_to_GIC.Data[3]

    reserved

    ENC_to_GIC.Data[4]

    Enclosure Azimuth Ready

    ENC_to_GIC.Data[5]

    Enclosure Altitude Ready

    ENC_to_GIC.Data[6]

    Enclosure Lower Maintenance trapped key in place

    ENC_to_GIC.Data[7]

    Enclosure Upper Maintenance trapped key in place

    ENC_to_GIC.Data[8]

    Enclosure Azimuth Motion Stopped

    ENC_to_GIC.Data[9]

    Enclosure Azimuth Safely Limited Speed

    ENC_to_GIC.Data[10]

    Enclosure Azimuth CW Limit

    ENC_to_GIC.Data[11]

    ReservedEnclosure Azimuth CCW Limit

    ENC_to_GIC.Data[12]

    Enclosure Altitude Motion Stopped

    ENC_to_GIC.Data[13]

    Enclosure Altitude local trapped key in place

    ENC_to_GIC.Data[14]

    Enclosure Altitude Upper Limit

    ENC_to_GIC.Data[15]

    Enclosure Altitude Lower Limit

    ENC_to_GIC.Data[16]

    Aperture Cover Closed

    ENC_to_GIC.Data[17]

    Aperture Cover local trapped key in place

    ENC_to_GIC.Data[18]

    Aperture Cover Closed Limit

    ENC_to_GIC.Data[19]

    Aperture Cover Open Limit

    ENC_to_GIC.Data[20]

    Bridge Crane Stowed

    ENC_to_GIC.Data[21]

    Bridge Crane local trapped key in place

    ENC_to_GIC.Data[22]

    reserved

    ENC_to_GIC.Data[23]

    reserved

    ENC_to_GIC.Data[24]

    Jib Crane Stowed

    ENC_to_GIC.Data[25]

    Jib Crane local trapped key in place

    ENC_to_GIC.Data[26]

    reserved

    ENC_to_GIC.Data[27]

    reserved

    ENC_to_GIC.Data[28]

    TEOA Platform Stowed

    ENC_to_GIC.Data[29]

    TEOA Platform local trapped key in place

    ENC_to_GIC.Data[30]

    reserved

    ENC_to_GIC.Data[31]

    reserved

    ENC_to_GIC.Data[32]

    Enclosure Azimuth aligned with maintenance position

    ENC_to_GIC.Data[33]

    Transfer Bridge Stowed

    ENC_to_GIC.Data[34]

    Transfer Bridge Rails Stowed

    ENC_to_GIC.Data[35]

    reserved

    ENC_to_GIC.Data[36]

    Rear Door local trapped key in place

    ENC_to_GIC.Data[37]

    reserved

    ENC_to_GIC.Data[38]

    reserved

    ENC_to_GIC.Data[39]

    reserved

    ENC_to_GIC.Data[40]

    Altitude Cable Wrap Overtension OK

    ENC_to_GIC.Data[41]

    Azimuth Cable Wrap Overtension OK

    ENC_to_GIC.Data[42]

    reserved

    ENC_to_GIC.Data[43]

    reserved

    ENC_to_GIC.Data[44]

    reserved

    ENC_to_GIC.Data[41]-->[127]

    not used

    GIC to Telescope LIC bit assignments

    The table below is the proposed structure for GIC to Enclosure communications.

    Tag Name

    Description

    GIC_to_TEL

     

    GIC_to_TEL.Connection_Status

     

    GIC_to_TEL.Data[0]

    Global Emergency Stop OK

    GIC_to_TEL.Data[1]

    Fire Alarm OK

    GIC_to_TEL.Data[2]

    Seismic Alarm OK

    GIC_to_TEL.Data[3]

    reserved

    GIC_to_TEL.Data[4]

    Reset Command from GIC

    GIC_to_TEL.Data[5]

    reserved

    GIC_to_TEL.Data[6]

    reserved

    GIC_to_TEL.Data[7]

    reserved

    GIC_to_TEL.Data[8]

    Inner Pier Hazardous Zone Locked

    GIC_to_TEL.Data[9]

    Mezzanine Level  Hazardous Zone Locked

    GIC_to_TEL.Data[10]

    Coudé Lab Hazardous Zone Locked

    GIC_to_TEL.Data[11]

    Utility Level Hazardous Zone Locked

    GIC_to_TEL.Data[12]

    Catwalk Hazardous Zone Locked

    GIC_to_TEL.Data[13]

    Service Ring Hazardous Zone Locked

    GIC_to_TEL.Data[14]

    Enclosure Floor Hazardous Zone Locked

    GIC_to_TEL.Data[15]

    Telescope Hazardous Zone Locked

    GIC_to_TEL.Data[16]

    Upper Enclosure Hazardous Zone Locked

    GIC_to_TEL.Data[17]

    reserved

    GIC_to_TEL.Data[18]

    reserved

    GIC_to_TEL.Data[19]

    reserved

    GIC_to_TEL.Data[20]

    Telescope Azimuth OK to move

    GIC_to_TEL.Data[21]

    Telescope Azimuth Full Speed OK

    GIC_to_TEL.Data[22]

    reserved

    GIC_to_TEL.Data[23]

    reserved

    GIC_to_TEL.Data[24]

    Telescope Altitude OK to move

    GIC_to_TEL.Data[25]

    Telescope Altitude Full Speed OK

    GIC_to_TEL.Data[26]

    reserved

    GIC_to_TEL.Data[27]

    reserved

    GIC_to_TEL.Data[28]

    M1 Cover OK to move

    GIC_to_TEL.Data[29]

    M1 Cover OK to open

    GIC_to_TEL.Data[30]

    reserved

    GIC_to_TEL.Data[31]

    reserved

    GIC_to_TEL.Data[32]-->[127]

    not used

    Telescope to GIC bit assignments

    Tag Name

    Description

    TEL_to_GIC

     

    TEL_to_GIC.Connection_Status

     

    TEL_to_GIC.Data[0]

    Telescope Mount Emergency Stop OK

    TEL_to_GIC.Data[1]

    Telescope Mount PLC I/O OK (LedStatus=3)

    TEL_to_GIC.Data[2]

    reserved

    TEL_to_GIC.Data[3]

    reserved

    TEL_to_GIC.Data[4]

    Telescope Mount Azimuth Ready

    TEL_to_GIC.Data[5]

    Telescope Mount Altitude Ready

    TEL_to_GIC.Data[6]

    Reserved

    TEL_to_GIC.Data[7]

    Reserved

    TEL_to_GIC.Data[8]

    Telescope Mount Azimuth Motion Stopped

    TEL_to_GIC.Data[9]

    Telescope Mount Azimuth at Safe Speed

    TEL_to_GIC.Data[10]

    Telescope Mount Azimuth CW Limit

    TEL_to_GIC.Data[11]

    Telescope Mount Azimuth CCW Limit

    TEL_to_GIC.Data[12]

    Telescope Mount Altitude Motion Stopped

    TEL_to_GIC.Data[13]

    Telescope Mount Altitude at Safe Speed

    TEL_to_GIC.Data[14]

    Telescope Mount Altitude Upper Limit

    TEL_to_GIC.Data[15]

    Telescope Mount Altitude Lower Limit

    TEL_to_GIC.Data[16]

    Reserved

    TEL_to_GIC.Data[17]

    Reserved

    TEL_to_GIC.Data[18]

    Reserved

    TEL_to_GIC.Data[19]

    Reserved

    TEL_to_GIC.Data[20]

    Telescope in M1 Maintenance Position Azimuth

    TEL_to_GIC.Data[21]

    Telescope in M1 Maintenance Position Altitude

    TEL_to_GIC.Data[22]

    Telescope in TEOA Maintenance Position Azimuth

    TEL_to_GIC.Data[23]

    Telescope in TEOA Maintenance Position Altitude

    TEL_to_GIC.Data[24]

    Reserved

    TEL_to_GIC.Data[25]

    Reserved

    TEL_to_GIC.Data[26]

    Reserved

    TEL_to_GIC.Data[27]

    Reserved

    TEL_to_GIC.Data[28]

    M1 Cover Closed

    TEL_to_GIC.Data[29]

    M1 Cart Jacks Stowed

    TEL_to_GIC.Data[30]

    M1 Cover permissive

    TEL_to_GIC.Data[31]

    Reserved

    TEL_to_GIC.Data[32]

    Telescope Altitude Hazardous Zones Locked

    TEL_to_GIC.Data[33]

    Telescope Azimuth Hazardous Zones Locked

    TEL_to_GIC.Data[34]

    Telescope Azimuth Cable Wrap Alignment OK

    TEL_to_GIC.Data[35]

    Reserved

    TEL_to_GIC.Data[36]

    OSS Bridge stowed

    TEL_to_GIC.Data[37]

    OSS Bridge permissive

    TEL_to_GIC.Data[38]

    M5 Bridge stowed

    TEL_to_GIC.Data[39]

    M5 Bridge permissive

    TEL_to_GIC.Data[40]

    Nasmyth Stairs Gates Closed

    TEL_to_GIC.Data[41]

    Telescope Floor Y+/- Gates Closed

    TEL_to_GIC.Data[42]

    Telescope Tower Doors Closed

    TEL_to_GIC.Data[43]

    Telescope Floor Hatch Closed

    TEL_to_GIC.Data[44]

    Reserved

    TEL_to_GIC.Data[45]-->[127]

    not used

    GIC to Coudé Rotator LIC bit assignments

    The table below is the proposed structure for GIC to Enclosure communications.

    Tag Name

    Description

    GIC_to_ROT

     

    GIC_to_ROT.Connection_Status

     

    GIC_to_ROT.Data[0]

    Global Emergency Stop OK

    GIC_to_ROT.Data[1]

    Fire Alarm OK

    GIC_to_ROT.Data[2]

    Seismic Alarm OK

    GIC_to_ROT.Data[3]

    Heartbeat

    GIC_to_ROT.Data[4]

    Reset Command from GIC

    GIC_to_ROT.Data[5]

    Reserved

    GIC_to_ROT.Data[6]

    reserved

    GIC_to_ROT.Data[7]

    reserved

    GIC_to_ROT.Data[8]

    Inner Pier Hazardous Zone Locked

    GIC_to_ROT.Data[9]

    Mezzanine Level  Hazardous Zone Locked

    GIC_to_ROT.Data[10]

    Coudé Lab Hazardous Zone Locked

    GIC_to_ROT.Data[11]

    Utility Level Hazardous Zone Locked

    GIC_to_ROT.Data[12]

    Catwalk Hazardous Zone Locked

    GIC_to_ROT.Data[13]

    Service Ring Hazardous Zone Locked

    GIC_to_ROT.Data[14]

    Enclosure Floor Hazardous Zone Locked

    GIC_to_ROT.Data[15]

    Telescope Hazardous Zone Locked

    GIC_to_ROT.Data[16]

    Upper Enclosure Hazardous Zone Locked

    GIC_to_ROT.Data[17]

    reserved

    GIC_to_ROT.Data[18]

    reserved

    GIC_to_ROT.Data[19]

    reserved

    GIC_to_ROT.Data[20]

    Coudé Azimuth OK to move

    GIC_to_ROT.Data[21]

    Coudé Azimuth Full Speed OK

    GIC_to_ROT.Data[22]

    reserved

    GIC_to_ROT.Data[23]

    reserved

    GIC_to_ROT.Data[24]-->[127]

    not used

    Coudé Rotator to GIC bit assignments

    Tag Name

    Description

    ROT_to_GIC

     

    ROT_to_GIC.Connection_Status

     

    ROT_to_GIC.Data[0]

    Rotator Emergency Stop OK

    ROT_to_GIC.Data[1]

    Rotator PLC I/O OK (LedStatus=3)

    ROT_to_GIC.Data[2]

    reserved

    ROT_to_GIC.Data[3]

    reserved

    ROT_to_GIC.Data[4]

    Rotator Azimuth Ready

    ROT_to_GIC.Data[5]

    reserved

    ROT_to_GIC.Data[6]

    reserved

    ROT_to_GIC.Data[7]

    reserved

    ROT_to_GIC.Data[8]

    Rotator Motion Stopped

    ROT_to_GIC.Data[9]

    Rotator at Safe Limited Speed

    ROT_to_GIC.Data[10]

    Rotator CW Final Limit OK (0=in limit)

    ROT_to_GIC.Data[11]

    Rotator CCW Limit OK  (0=in limit)

    ROT_to_GIC.Data[12]

    reserved

    ROT_to_GIC.Data[13]

    reserved

    ROT_to_GIC.Data[14]

    reserved

    ROT_to_GIC.Data[15]

    reserved

    ROT_to_GIC.Data[16]

    reserved

    ROT_to_GIC.Data[17]

    reserved

    ROT_to_GIC.Data[18]

    reserved

    ROT_to_GIC.Data[19]

    reserved

    ROT_to_GIC.Data[20]

    Rotator Cable Wrap Alignment OK

    ROT_to_GIC.Data[21]

    reserved

    ROT_to_GIC.Data[22]

    reserved

    ROT_to_GIC.Data[23]

    reserved

    ROT_to_GIC.Data[24]

    reserved

    ROT_to_GIC.Data[25]

    reserved

    ROT_to_GIC.Data[26]

    reserved

    ROT_to_GIC.Data[27]

    reserved

    ROT_to_GIC.Data[28]

    reserved

    ROT_to_GIC.Data[29]

    reserved

    ROT_to_GIC.Data[30]

    reserved

    ROT_to_GIC.Data[31]

    reserved

    ROT_to_GIC.Data[32]

    reserved

    ROT_to_GIC.Data[33]

    reserved

    ROT_to_GIC.Data[34]

    reserved

    ROT_to_GIC.Data[35]

    reserved

    ROT_to_GIC.Data[36]

    reserved

    ROT_to_GIC.Data[37]

    reserved

    ROT_to_GIC.Data[38]

    reserved

    ROT_to_GIC.Data[39]

    reserved

    ROT_to_GIC.Data[40]

    reserved

    ROT_to_GIC.Data[41]-->[127]

    not used

     

    Optical Subsystem (OSS) to GIC bit assignments

    Tag Name

    Description

    OSS_to_GIC

     

    OSS_to_GIC.Connection_Status

     

    OSS_to_GIC.Data[0]

    OSS Emergency Stop OK

    OSS_to_GIC.Data[1]

    OSS PLC I/O OK (LedStatus=3)

    OSS_to_GIC.Data[2]

    reserved

    OSS_to_GIC.Data[3]

    reserved

    OSS_to_GIC.Data[4]

    reserved

    OSS_to_GIC.Data[5]

    reserved

    OSS_to_GIC.Data[6]

    reserved

    OSS_to_GIC.Data[7]

    reserved

    OSS_to_GIC.Data[8]

    On Sun

    OSS_to_GIC.Data[9]

    reserved

    OSS_to_GIC.Data[10]

    reserved

    OSS_to_GIC.Data[11]

    reserved

    OSS_to_GIC.Data[12]

    reserved

    OSS_to_GIC.Data[13]

    reserved

    OSS_to_GIC.Data[14]

    reserved

    OSS_to_GIC.Data[15]

    Reserved

    OSS_to_GIC.Data[16]

    Heat Stop Shutter is fully open

    OSS_to_GIC.Data[17]

    Heat Stop Shutter is fully closed

    OSS_to_GIC.Data[18]

    Heat Stop Safety Shutter permissive

    OSS_to_GIC.Data[19]

    Heat Stop Temperature is OK

    OSS_to_GIC.Data[20]

    Heat Stop Coolant Pressure is OK

    OSS_to_GIC.Data[21]

    Reserved

    OSS_to_GIC.Data[22]

    Reserved

    OSS_to_GIC.Data[23]

    Reserved

    OSS_to_GIC.Data[24]

    Heat Stop is installed

    OSS_to_GIC.Data[25]

    M2 is installed

    OSS_to_GIC.Data[26]

    Reserved

    OSS_to_GIC.Data[27]

    reserved

    OSS_to_GIC.Data[28]

    reserved

    OSS_to_GIC.Data[29]

    reserved

    OSS_to_GIC.Data[30]

    reserved

    OSS_to_GIC.Data[31]

    reserved

    OSS_to_GIC.Data[32]

    M5 Temperature is OK.

    OSS_to_GIC.Data[33]

    reserved

    OSS_to_GIC.Data[34]

    reserved

    OSS_to_GIC.Data[35]

    reserved

    OSS_to_GIC.Data[36]

    reserved

    OSS_to_GIC.Data[37]

    reserved

    OSS_to_GIC.Data[38]

    reserved

    OSS_to_GIC.Data[39]

    reserved

    OSS_to_GIC.Data[40]

    reserved

    OSS_to_GIC.Data[41]

    reserved

    OSS_to_GIC.Data[42]

    reserved

    OSS_to_GIC.Data[43]

    reserved

    OSS_to_GIC.Data[44]

    reserved

    OSS_to_GIC.Data[41]-->[127]

    not used

    GIC to OSS LIC bit assignments

    Tag Name

    Description

    GIC_to_OSS

     

    GIC_to_OSS.Connection_Status

     

    GIC_to_OSS.Data[0]

    GIC Emergency Stop is OK

    GIC_to_OSS.Data[1]

    GIC Fire Alarm is OK

    GIC_to_OSS.Data[2]

    GIC Seismic Alarm is OK

    GIC_to_OSS.Data[3]

    reserved

    GIC_to_OSS.Data[4]

    GIC reset

    GIC_to_OSS.Data[5]

    Light Path is blocked

    GIC_to_OSS.Data[6]

    reserved

    GIC_to_OSS.Data[7]

    reserved

    GIC_to_OSS.Data[8]

    Safety Shutter open permissive (0=shutter must close)

    GIC_to_OSS.Data[9]

    reserved

    GIC_to_OSS.Data[10]

    reserved

    GIC_to_OSS.Data[11]

    reserved

    GIC_to_OSS.Data[12]

    reserved

    GIC_to_OSS.Data[13]

    reserved

    GIC_to_OSS.Data[14]

    reserved

    GIC_to_OSS.Data[15]

    Reserved

    GIC_to_OSS.Data[16]

    reserved

    GIC_to_OSS.Data[17]

    reserved

    GIC_to_OSS.Data[18]

    reserved

    GIC_to_OSS.Data[19]

    reserved

    GIC_to_OSS.Data[20]

    reserved

    GIC_to_OSS.Data[21]

    reserved

    GIC_to_OSS.Data[22]

    reserved

    GIC_to_OSS.Data[23]

    reserved

    GIC_to_OSS.Data[24]

    reserved

    GIC_to_OSS.Data[25]

    reserved

    GIC_to_OSS.Data[26]

    reserved

    GIC_to_OSS.Data[27]

    reserved

    GIC_to_OSS.Data[28]

    reserved

    GIC_to_OSS.Data[29]

    reserved

    GIC_to_OSS.Data[30]

    reserved

    GIC_to_OSS.Data[31]

    reserved

    GIC_to_OSS.Data[32]

    reserved

    GIC_to_OSS.Data[33]

    reserved

    GIC_to_OSS.Data[34]

    reserved

    GIC_to_OSS.Data[35]

    reserved

    GIC_to_OSS.Data[36]

    reserved

    GIC_to_OSS.Data[37]

    reserved

    GIC_to_OSS.Data[38]

    reserved

    GIC_to_OSS.Data[39]

    reserved

    GIC_to_OSS.Data[40]

    reserved

    GIC_to_OSS.Data[41]-->[127]

    not used

    Instrument LIC to GIC bit assignments

    Tag Name

    Description

    INST_to_GIC

     

    INST_to_GIC.Connection_Status

     

    INST_to_GIC.Data[0]

    Instruments Emergency Stop OK

    INST_to_GIC.Data[1]

    Instruments PLC I/O OK (LedStatus=3)

    INST_to_GIC.Data[2]

    Reserved

    INST_to_GIC.Data[3]

    Reserved

    INST_to_GIC.Data[4]

    Reserved

    INST_to_GIC.Data[5]

    Reserved

    INST_to_GIC.Data[6]

    Reserved

    INST_to_GIC.Data[7]

    Reserved

    INST_to_GIC.Data[8]

    Reserved

    INST_to_GIC.Data[9]

    Reserved

    INST_to_GIC.Data[10]

    Reserved

    INST_to_GIC.Data[11]

    Reserved

    INST_to_GIC.Data[12]

    Reserved

    INST_to_GIC.Data[13]

    Reserved

    INST_to_GIC.Data[14]

    Reserved

    INST_to_GIC.Data[15]

    Reserved

    INST_to_GIC.Data[16]

    Reserved

    INST_to_GIC.Data[17]

    Reserved

    INST_to_GIC.Data[18]

    Reserved

    INST_to_GIC.Data[19]

    Reserved

    INST_to_GIC.Data[20]

    Reserved

    INST_to_GIC.Data[21]

    Reserved

    INST_to_GIC.Data[22]

    Reserved

    INST_to_GIC.Data[23]

    Reserved

    INST_to_GIC.Data[24]

    Reserved

    INST_to_GIC.Data[25]

    Reserved

    INST_to_GIC.Data[26]

    Reserved

    INST_to_GIC.Data[27]

    Reserved

    INST_to_GIC.Data[28]

    Reserved

    INST_to_GIC.Data[29]

    Reserved

    INST_to_GIC.Data[30]

    Reserved

    INST_to_GIC.Data[31]

    Reserved

    INST_to_GIC.Data[32]

    Reserved

    INST_to_GIC.Data[33]

    Reserved

    INST_to_GIC.Data[34]

    Reserved

    INST_to_GIC.Data[35]

    Reserved

    INST_to_GIC.Data[36]

    Reserved

    INST_to_GIC.Data[37]

    Reserved

    INST_to_GIC.Data[38]

    Reserved

    INST_to_GIC.Data[39]

    Reserved

    INST_to_GIC.Data[40]

    Reserved

    INST_to_GIC.Data[41]

    Reserved

    INST_to_GIC.Data[42]

    Reserved

    INST_to_GIC.Data[43]

    Reserved

    INST_to_GIC.Data[44]

    Reserved

    INST_to_GIC.Data[41]-->[127]

    not used