Enclosure Aperture Cover Timeout Fault details

Enclosure Aperture Cover Timeout Fault details

Recurring problem with GIS Aperture Cover Interlock:

To protect M1, under one of several conditions, GIS sends a ‘Close AP Cover’ to ENC _LIC / EMCS PLC

When GIC commands Aperture Cover to close it cannot be opened until GIS Reset.

When Aperture cover reaches either limit the drive control unit issues a fault. Drives are not operable until faults are cleared by EMCS Reset.

Aperture cover drives stop when end of travel limit sensors are active. The same sensors report position to EMCS, the drive control unit and ENC_LIC (via separate inputs).

135 seconds after GIC commands Aperture Cover closed', if the Aperture Cover is not closed, a fault is issued. This requires GIS Fault Reset. By a quirk of the logic GIS reset must be issued two times.

TLDR

When GIC commands Aperture Cover to close, then at the end of the movement:
Click EMCS Reset (from HMI or pendant)
Click GIS reset from TIM HMI.

Use only the the graphical GIS reset icon on the TIM HMI. Other reset buttons will not reset faults.

Wait a few seconds.
Click GIS reset from TIM HMI again.

The GIS must be reset twice to clear all faults.

Related content

Temporary Aperture Cover Bypass Procedure
Temporary Aperture Cover Bypass Procedure
More like this
Light Path Safety Function
Light Path Safety Function
Read with this
M1 Cover Fault during closing
M1 Cover Fault during closing
More like this
Aperture Cover close Timeout fault
Aperture Cover close Timeout fault
More like this
Aperture Cover Closing
Aperture Cover Closing
More like this
GIS reset vs. GIS fault reset
GIS reset vs. GIS fault reset
More like this